6.5.13 Setting the 4 mA output
Provides for the precise adaptation of the output 4.0000 mA signal
to the 4.0000 mA input of a higher-order management system
A0607
Fig. 29: Setting the 4 mA output
Function
Options
Information
Setting the 4 mA output
- 200 ... + 200
Adjust the mA value to adapt to a higher-level control
(e.g. PLC or SCADA)
One number corresponds to 0.001 mA
6.5.14 Setting the 20-mA output
Provides for the precise adaptation of the output 20.0000 mA
signal to the 20.0000 mA input of a higher-order management
system
A0608
Fig. 30: Setting the 20-mA output
Function
Options
Information
Setting the 20-mA output
- 1000 ... + 1000
Adjust the mA value to adapt to a higher-level control
(e.g. PLC or SCADA)
One number corresponds to 0.001 mA
Commissioning