Make the following settings on the UREG200:
IN1U = PU,
DP1 = NODP,
IN2U = PU,
DP2 = NODP,
FUNC = FULL,
COMM = 4-20,
AOFN = P1-2,
AOLO = -100,
AOHI = 100
7.10 Digital filter
In some applications the process value is too unstable to
be shown directly on the display. To remedy this, a digital
filter is integrated in the UREG200, which can be adjusted
as required. The filter works with a time constant of first
priority and is set in the setup menu, the parameter is FILT.
The factory setting is 0.5 sec, the setting range is from 0
(disabled) to 60 sec. Please refer to the picture for the filter
property.
Filter behavior
Note:
The filter is only available for the display of PV1 and is only effective
for the display of the process value. The UREG200 is designed to
process unfiltered signals.
7.11 Sleep mode
To enable the sleep mode, proceed as follows:
Setup-menu-settings
FUNC = FULL
SLEP = YES
Switch on sleep mode:
Press
for 3 sec. to switch on the sleep mode.
Menu
FILT
The filter is used to
stabilize the
process display