6.6 Heating-cooling control
Six different controller configurations can be set for the heating-cooling control.
Please refer to the following table for the parameter settings:
Note:
The ON-OFF control can lead to strong process fluctuations.
The P (PD) control can also lead to slight deviations from the setpoint. For a
stable and low-deviation process result, the PID heating-cooling control is
required.
Further settings required:
O1TY, CYC1, O2TY, CYC2, A2SP, A2DV,
O1TY & O2TY are set depending on the control configuration.
CYC1 & CYC2 depending on O1TY resp. O2TY
Typical settings OUT1 /OUT2:
output SSR: CYC1/CYC2 = 0,5
~
2 sec.
output relay: O1TY/O2TY = 10
~
20 sec.
Analogue output:
CYC1/CYC2 = not adjustable (hidden)