6.3 Setting the User Menu (SEL1
– SEL5)
The UREG200 is equipped with a flexible user menu. In order to reach
frequently used parameters quickly, it is possible to place them in front
of the actual menu. These can be stored in the parameters SEL1 to
SEL5 in an application-optimised manner:
SEL1
: For the most frequently required parameter
SEL2
: For the second most frequently required parameter
SEL3
: For the third most frequently required parameter
SEL4
: For the fourth most frequently required parameter
SEL5
: For the fifth most frequently required parameter
Range: NONE, TIME, A1.SP, A1.DV, A2.SP, A2.DV, RAMP,
OFST, REFC, SHIF, PB1, TI1, TD1, C.PB, DB, SP2, PB2, TI2, TD2
Parameters that are hidden due to settings cannot be selected.
6.4 Heating only control
Heating ON-OFF control:
Select REVR for OUT1, set PB1 to 0, SP1 is the setpoint,
O1HY is the ON-OFF hysteresis, TIME is for setting the
heating time.
Note:
The TIMR parameter in A1FN or A2FN cannot be
selected with this setting, the output 1 hysteresis (O1HY)
can only be set if
PB1 = 0.
The heating ON-OFF control is shown in the following diagram:
Heating ON-OFF control
Setting ON-OFF:
OUT1 =
PB1 = 0
Parameter:
SP1, O1HY, TIME