Service setting manual
48
ENG
Para-
meter
Parameter name
Parameter description
Setting range
Default
setting
S6.6
OPERATION OF LIQUID
FUEL BOILER
Setting if d. h. w. warming with oil boiler and solar collectors or solid
fuel boiler can operate at the same time or oil boiler shall activate
with delay after warming with solar collectors or solid fuel boiler has
been stopped.
-1- PARALELL
0 ÷ 600 MIN-
DELAY OF
LIQUID FUEL
BOILER
120
S6.7
CIRCUITS WITH DELAYED
ACTIVATION OF LIQUID
FUEL BOILER
Selection of circuits where oil boiler shall activate with delay after
warming with solar collectors or solid fuel boiler.
1- domestic hot water
2- heating circuits
3- domestic hot water and heating circuits
1- D. H. W.
2- CIRCUITS
3- BOTH
1
S6.8
SOLAR PUMP KICK FUNC-
TION
Special algorithm activates the solar pump to switch -on for short
intervals. This way realistic temperature of collectors is obtained.
This function is used especially with vacuum (tube) collectors or
with classic collectors if the sensor is fitted outside of the collector
body.
0- NO
1- YES
0
S6.9
RESPECT MIN. TEMPERA-
TURE OF COLLECTORS OR
SOLID FUEL BOILER
We define whether and how the minimum collector or solid fuel
boiler temperature is respected.
0- NO
1- YES
2- YES, SWITCH
-ON
2
S6.10
OPERATION MODE OF
COLLECTORS OR SOLID
FUEL BOILER CIRCULATI-
ON PUMP
Setting of circulation pump ON/OFF or RPM operation mode. RPM
modulation of the pump is done with 5 stages (40 %, 55 %, 70 %,
85 %, 100 % RPM).
0- ON/OFF
1- RPM
1
S6.11
MINIMUM RPM FOR PUMP
Minimum RPM stage for modulation of circulation pump.
1- 40 % RPM
2- 55 % RPM
3- 70 % RPM
1- 40 %
2- 55 %
3- 70 %
1
S6.12
FULL-RPM RUNNING TIME
OF COLLECTORS OR SOLID
FUEL BOILER CIRCULATI-
ON PUMP
When the differential condition is fulfilled, the circulation pump runs
at max. RPM for a setted time. Afterwards the pump is running with
RPM modulation (if enabled with parameter S6.10=1).
5 ÷ 300 s
20
S6.13
LOCATION OF COLD SEN-
SOR FOR DIFF. THERMO-
STAT
Cold sensor (T8) place of mount, if it is being used for differential
thermostat. In exact we define storage device which is being
warmed with solar collectors or solid fuel boiler.
1- D. H. W.
TANK
2- HEAT AC-
CUMULATOR
1
S6.14
HEAT PUMP- OPERATION
MODE
Setting if heat pump should operate in ON/OFF or weather com-
penstaed mode.
1- ON/OFF
2- WEATHER
COMPENSATED
2
S6.15
HEAT PUMP - MAX. SUPPLY
WATER TEMPERATURE
Setting of max. heat pump output temperature when operating in
weather compenstaed mode.
40 ÷ 70 °C
50
S6.16
HEAT PUMP - OPERATION
HYSTERESIS
Setting of hysteresis for heat pump operation.
2 ÷ 10 °C
4
S6.17
HEAT PUMP - MIN. OUTDO-
OR TEMP. FOR HEAT PUMP
OPERATION
Setting of min. outdoor temperature below which the heat pump
should switch off.
-30 ÷ 20 °C
-10
S6.5
COLLECTOR’S FROST
PROTECTION TEMPERATU-
RE
Setting of temperature by which the collector's frost protection
should activate.
-20 ÷ 10 °C
4