Service setting manual
39
ENG
General service settings:
Para-
meter
Parameter name
Parameter description
Setting range Default
setting
S1.1
HYDRAULIC SCHE-
ME
Selection of hydraulic scheme.
depends on
type of con-
troller
/
S1.2
CODE FOR UNLOC-
KING THE SERVICE
SETTINGS
This setting enables the change of code which is necessary to unlock the
service settings (S and F parameters).
WARNING! Keep new code on a safe place. Without this code is impossible to
change service settings.
0000 - 9999
0001
S1.3
TEMPERATURE
SENSOR TYPE
Selection of temperature sensors Pt1000 or KTY10.
0- PT1000
1- KTY10
0
S1.4
T1 SENSOR FUNC-
TION
Selection of function for sensor connected to input T1.
1- RF, room sensor in circuit 1
2- EF1, sensor for limitation of max. floor temperature in circuit 1. Max. floor
temperature is set with parameter S2.11.
3- RLF1, return pipe sensor in circuit 1. Activates limitation of difference
between stand and return pipe and by that the limitation of max. heating circuit
power. Max. difference is set with parameter S2.14.
4- KTF, sensor in solar collectors. Activates the solar differential thermostat.
(Cold sensor for differential thermostat is T8, pump is controlled with output
R6, operation mode is set with parameters P6 and S6).
5- KF2, sensor in solid fuel boiler. Activates the solid fuel boiler differential
thermostat. (Cold sensor for differential thermostat is T8, pump is controlled
with output R6, operation mode is set with parameters P6 and S6).
6- BF3, d. h. w circulation with temperature sensor. Sensor is placed onto (hot)
exit pipe from storage tank. D. h. w. circulation pump is activated if temperatu-
re increase is detected. Duration time of circulation is set with parameter P4.8.
7- SVS, d. h. w. circulation with flow switch. D. h. w. circulation pump is activa-
ted if contact are closed. Duration time of circulation is set with parameter
P4.8.
8- BF2, auxiliary sensor in d .h. w. storage tank. It is installed in upper third of
storage tank. Warming of d. h. w. will activate only when BF2 sensor detects
drop of temperature.
9- AGF, flue gas temperature sensor for boiler. Warning is displayed on the
screen, if flue gas temperature rises above value of parameter S5.18.
10- RFHP, room sensor in ambient where d. h.w. heat pump is installed. D. h.
w. warming with other heat sources is disabled if room temperature is higher
as set with parameter S4.11.
11- RLKF, boiler return-pipe sensor. Controller maintains min. level of boiler
return-pipe temperature set with parameter S5.14. For this setting it is neces-
sary to have a hydraulic system with primary boiler circulation pump or hydrau-
lic system with boiler bypass pump (parameter S4.9=4).
12- AGFTK, flue gases sensor for solid fuel boiler. Controller blocks liquid fuel
boiler operation if flue gases exceed temperature setted with parameter S5.19.
1- RF1
2- EF1
3- RLF1
4- KTF
5- KF2
6- BF3
7- SVS
8- BF2
9- AGF
10- RFHP
11- RLKF
12- AGFTK
1