
50
10 Supplement
VEGASON 62 • Profibus PA
28785-EN-150603
10 Supplement
10.1 Technical data
General data
Materials, wetted parts
Ʋ Transducer
PVDF
Ʋ Seal transducer/process fitting
EPDM, FKM
Ʋ Process fitting G2 DIN3852-A-B
PVDF
Ʋ Process fitting 2 NPT
ASME B1.20.1
Materials, non-wetted parts
Ʋ
Housing
Plastic PBT (polyester), Alu die-casting, powder-coated,
316L
Ʋ Seal between housing and housing
cover
NBR (stainless steel housing), silicone (Alu/plastic hous
-
ing)
Ʋ Inspection window in housing cover
Polycarbonate
Ʋ Ground terminal
316Ti/316L
Weight
1.8 … 4 kg (4 … 8.8 lbs), depending on the process
fitting and housing
Max. torque mounting boss
25 Nm
Output variable
Output signal
digital output signal, format according to IEEE-754
Cycle time
min. 1 s (dependent on the parameter setting)
Sensor address
126 (default setting)
Current value
10 mA, ±0.5 mA
Damping (63 % of the input variable)
0 … 999 s, adjustable
Met NAMUR recommendation
NE 43
Resolution, digital
> 1 mm (0.039 in)
Input variable
Measured variable
distance between lower edge of the transducer and
product surface
Measuring range
Ʋ Liquids
up to 8 m (26.25 ft)
Ʋ Bulk solids
up to 3.5 m (11.48 ft)
Dead zone
0.4 m (1.312 ft)
Reference conditions to measuring accuracy (according to DIN EN 60770-1)
Reference conditions according to DIN EN 61298-1
Ʋ
Temperature
+18 … +30 °C (+64 … +86 °F)
Ʋ Relative humidity
45 … 75 %
Ʋ
Air pressure
860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)