VEGASON 62 • Profibus PA
28785-EN-150603
Warning:
The housing must not be used to screw the instrument in! Applying
tightening force can damage internal parts of the housing.
When mounting the sensor, keep a distance of at least 200 mm
(7.874 in) to the vessel wall. If the sensor is installed in the center of
dished or round vessel tops, multiple echoes can arise. These can,
however, be suppressed by an appropriate adjustment (see chapter
"
Setup
").
1
2
> 200 mm
Fig. 5: Mounting on round vessel tops
1 Reference plane
2 Vessel center or symmetry axis
If this distance cannot be maintained, a false signal storage should
be carried out during setup. This applies particularly if buildup on the
vessel wall is expected. In such cases, we recommend repeating the
false signal storage at a later date with existing buildup.
In vessels with conical bottom it can be advantageous to mount the
sensor in the center of the vessel, as measurement is then possible
down to the lowest point of the vessel bottom.