PD6700-0L1 Field-Mount Loop-Powered Process Meter
Instruction Manual
5
Specifications
Except where noted all specifications apply to operation at +25°C.
General
Display
Five digits
(-9999 to
99999)
0.60" (15.2 mm) high,
7-segment,
automatic lead zero
blanking.
Seven
characters
0.4" (10.2 mm) high,
14-segment.
Symbols
Bargraph which displays
process input from
0-100% of scaled value.
Display
Orientation
Display may be mounted at 90° increments
up to 270° from default orientation.
Display
Assignment
Lower display may be assigned to custom unit
or tag, volume, volume and tag, percent height,
percent height and tag, or off.
Display
Update Rate
Ambient > -25°C: 2 Updates/Second
Ambient < -25°C: 1 Update/5 Seconds
Backlight
White; Loop-powered or externally powered.
Backlight can be enabled or disabled via
alternative wiring of terminal block. Loop-
powered backlight brightness will increase as
the input signal current increases. Externally
powered backlight has consistent brightness.
Externally
Powered
Backlight
Voltage
Range:
Maximum Power
9-36
VDC
9
VDC
12
VDC
24
VDC
36
VDC
0.2 W
0.25 W
0.5 W
0.75 W
Display
Overrange
Display flashes
99999
Display
Underrange
Display flashes
-9999
Programming
Method
Four SafeTouch through-window buttons when
cover is installed. Four internal pushbuttons
when cover is removed.
Noise Filter
Programmable
LO
,
med
,
HI
, or
OFF
Recalibration
Recalibration is recommended at least every
12 months.
Max/Min
Display
Max/Min readings reached by the process are
stored until reset by the user or until power to
the meter is turned off.
Advanced
Function
Linear, square root, or programmable
exponent
Password
Programmable password restricts modification
of programmed settings.
Non-Volatile
Memory
All programmed settings are stored in non-
volatile memory for a minimum of ten years if
power is lost.
Normal Mode
Rejection
64 dB at 50/60 Hz
Environmental
Operating temperature range: -40 to 75°C
Storage temperature range: -40 to 75°C
Relative humidity: 0 to 90%
non-condensing
Connections
Screw terminals accept 12 to 22 AWG wire
Enclosure
NEMA 4X, IP65 plastic field enclosure
Color: grey
Three ¾" NPT threaded conduit openings.
Two ¾" NPT plastic conduit/stopping plugs
with 1.29" wrenching flats and screwdriver
slot.
Mounting
May be mounted directly to conduit. Two
slotted flanges for wall mounting or NPS
1½" to 2½" or DN 40 to 65 mm pipe
mounting. See
Dimensions
on page
6
.
Overall
Dimensions
5.67" x 5.25" x 4.18" (W x H x D)
(144 mm x 133 mm x 106 mm)
Weight
1.65 lbs (26.4 oz, 0.75 kg)
Warranty
3 years parts and labor. See Warranty
Information and Terms & Conditions on
www.predig.com
for complete details.
Input
Input
4-20 mA
Accuracy
±0.03% of calibrated span ±1 count,
square root & programmable exponent
accuracy range:
10-100% of calibrated span.
Maximum
Voltage Drop &
Equivalent
Resistance
Without Backlight
or with Externally
Powered Backlight
With Loop-Powered
Backlight
3.0 VDC @ 20 mA
6.0 VDC @ 20 mA
150
Ω @ 20 mA
300
Ω @ 20 mA
Temperature Drift
50 PPM/
C from -40 to 75
C ambient
Multi-Point
Linearization
2 to 32 points
Decimal Point
User selectable decimal point
Minimum Span
Input 1 & Input 2: 0.10 mA
Calibration Range
An
Error
message will appear if input 1 and
input 2 signals are too close
together.
Input
Range
Minimum Span
Input 1 & Input 2
4-20 mA
0.10 mA
Input
Overload
Over current protection to 2 A max.
HART
Transparency
The meter does not interfere with existing
HART communications; it displays the 4-20
mA primary variable and it allows the
HART communications to pass through
without interruption.
The meter is not affected if a HART
communicator is connected to the loop.
The meter does not display secondary
HART variables.
Open Collector Output
Rating
Isolated open collector, sinking NPN
30 VDC @ 150 mA max.
Alarm Output
Assign to level or volume for high or low
alarm trip point.
Deadband
0-100% FS, user selectable
Acknowledge
Front panel ENTER button and external
RESET terminals resets output and screen
indication.