PD6700-0L1 Field-Mount Loop-Powered Process Meter 

Instruction Manual 

 

17

 

Alarm Output (

OUTPUT

The PD6700-0L1 is equipped with an NPN open 
collector output that may be set up for high or low 
alarm trip point based on the level display (

LEVEL

) or 

the volume scale (

VOLUME

). The output may be 

disabled by selecting 

OFF

When the alarm is enabled for level and the alarm set 
point has been reached, the level display will flash, 
accompanied by the lower display alternating 
between normal display and 

ALARM

. A tank height 

indicator segment will flash at the level the alarm is 
set to while the level indicator is at or above the alarm 
point. 
When the alarm is enabled for volume and the alarm 
set point has been reached, the lower display will 
flash, alternating between its normal display and 

ALARM

To set a high alarm, program the set point value to be 
greater than the reset point. 

To set a low alarm, program the set point value to be 
less than the reset point. 
To acknowledge an alarm, press the 

ENTER

 button 

once for acknowledge prompt and a second time to 
confirm. Acknowledging an alarm will turn off the 
alarm output and stop the display from flashing. The 
lower display will continue to alternate between its 
normal display and ALARM until the alarm condition is 
cleared. 
The alarm status will show on the display even if the 
output is not wired. 

 

Input Signal Filter (

FILTER

The noise filter is available for unusually noisy signals 
that cause an unstable process variable display. The 
noise filter averages the input signal over a certain 
period. The filter level can be set to low (

LO

), medium 

(

MED

), high (

HI

), or off (

OFF

). The higher the filter 

setting, the longer the averaging time and so the 
longer the display may take to find its final value. 
The filter contains a noise filter bypass feature so that 
while small variations in the signal will be filtered out, 
large, abrupt changes to the input signal are 
displayed immediately. 

 

Volume Display Scaling (

VOLSCAL

Volume may be scaled as a function of the level 
display. It may use up to 32-point linearization. The 
multi-point linearization can be used to linearize the 
display for non-linear signals such as those from level 
transmitters used to measure volume in odd-shaped 
tanks. 

To scale the volume display, select the decimal point 
location (0, 1, 2, 3, or 4), then enter the level in 
engineering units for input 1, the corresponding 
volume display value, and the same for input 2. 
After entering the display 2 value, confirm the new 
volume scale by pressing 

ENTER

 at the 

Save

 menu. 

 

 

 

Note: 

To display the volume, see Configuring the Display 

(

DISPLAY

)

 on page 13. 

 

 

 

Summary of Contents for vantageview Safe Touch PD6700-0L1

Page 1: ...r Display Display Mountable at 0 90 180 270 SafeTouchTM Through Window Button Programming Display Input in Two Different Scales Simultaneously Great for Level Applications 20 Segment Level Indicator B...

Page 2: ...Precision Digital Corporation All rights reserved Introduction The PD6700 0L1 is a rugged field mount loop powered meter fully featured for demanding applications in harsh environmental conditions Th...

Page 3: ...ing the Meter SCaLe 13 Minimum Input Span 13 Scale Error Message SPN ERR 13 Scaling the Tank Level Indicator PERCENT 13 Configuring the Display DISPLAY 13 Setting the Tag TAG 14 Setting Up the Passwor...

Page 4: ...imensions Side Cross Section View 6 Figure 3 Connector Board 7 Figure 4 Connections without Backlight 8 Figure 5 Connections with Loop Powered Backlight 8 Figure 6 Connections with Externally Powered...

Page 5: ...ntal Operating temperature range 40 to 75 C Storage temperature range 40 to 75 C Relative humidity 0 to 90 non condensing Connections Screw terminals accept 12 to 22 AWG wire Enclosure NEMA 4X IP65 pl...

Page 6: ...e the meter from box Inspect the packaging and contents for damage Report damages if any to the carrier If any part is missing or the meter malfunctions please contact your supplier or the factory for...

Page 7: ...ght from external supply OUTPUT NPN open collector output positive OUTPUT NPN open collector output negative RESET Contact closure alarm acknowledge pull up to 3 VDC RESET Contact closure alarm acknow...

Page 8: ...e to two terminals labeled RESET Connect to a contact closure source such as a relay or a pushbutton as shown in Figure 7 Figure 7 External Alarm Reset Acknowledge Connections Open Collector Output Co...

Page 9: ...rd in the base of the enclosure SafeTouch Button Operation To actuate a button press and remove one finger to the window directly over the marked button area Remove finger to at least 4 inches away fr...

Page 10: ...the Right arrow button to reset the maximum or minimum value while it is being displayed see Up Display Button below Press the Right arrow button to move to the next digit or decimal position during p...

Page 11: ...play Enter Bottom Display menu TAG Tag Display a custom unit or tag VOLUME Volume Display volume VOL TAG Volume Tag Display volume and custom tag PCT HT Percent Height Display percent height PCT TAG P...

Page 12: ...o the previous menu selections Setting Numeric Values The numeric values are set using the RIGHT and UP arrow buttons Press RIGHT arrow to select next digit and UP arrow to increment digit The digit b...

Page 13: ...nearization MULTIPT menu selection prior to scaling and calibration of the meter see Advanced Features Menu ADVANCE on page 15 Scaling the Tank Level Indicator PERCENT The display includes a 20 segmen...

Page 14: ...recorded in the space provided Model Serial Number Password __ __ __ __ __ Making Changes to a Password Protected Meter If the meter is password protected the meter will display the message LOCKED wh...

Page 15: ...Menu Access the Advanced Features Menu by pressing ENTER at the ADVANCE menu in the Main Menu defined on page 11 The Advanced Features Menu is used to select 1 Open collector output configuration OUTP...

Page 16: ...NPUT 1 Input 1 Set volume input 1 on the level display DSPLY 1 Display 1 Set volume display 1 INPUT 2 Input 2 Set volume input 2 on the level display DSPLY 2 Display 2 Set volume display 2 Display Par...

Page 17: ...etween its normal display and ALARM until the alarm condition is cleared The alarm status will show on the display even if the output is not wired Input Signal Filter FILTER The noise filter is availa...

Page 18: ...ve a full scale accuracy of 0 002 or better between 4 and 20 mA in order to maintain the specified accuracy of the meter 2 Allow the meter to warm up for at least 15 minutes before performing the cali...

Page 19: ...s displayed will reset that value to the current display value Press the DISPLAY button a third time and the meter will display LOOP MA on the lower display and the measured input current in milliamps...

Page 20: ...e Diagnostics menu and consult the recommendations described in the following table Troubleshooting Tips Symptom Check Action No display or faint display Check input signal connections Perform hard re...

Page 21: ...tion or increment digit Cycle through maximum minimum and mA display mode ENTER Accept selection value and move to next selection Acknowledge alarms To enter the Advanced Features Menu hold the Menu b...

Page 22: ...8990 www predig com LIM6700L_D SFT087 Ver 1 300 up 07 20 Contact Precision Digital Technical Support Call 800 610 5239 or 508 655 7300 Fax 508 655 8990 Email support predig com Sales Support Call 800...

Reviews: