PD663 Loop-Powered Meter
Instruction Manual
9
Product Ratings and Approvals
FM
Class I, Division 1, Groups B, C, D
Class II, Division 1, Groups E, F, G
Class III, Division 1; T6
Class I, Zone 1, AEx d IIC T6 Gb
Zone 21, AEx tb IIIC T85°C
Ta = -40°C to +75°C
Enclosure: Type 4X & IP66
Certificate number: 3040391
ATEX
II 2 G D
Ex d IIC T6 Gb
Ex tb IIIC T85°C Db IP68
Ta = -40°C to +75°C
ATEX Certificate: Sira 10ATEX1116X
CSA
Class I, Division 1, Groups B, C, D
Class II, Division 1, Groups E, F, G
Class III, Division 1; T6
Class I, Zone 1, Ex d IIC T6
Ta = -40°C to +75°C
Enclosure: Type 4X & IP66
Certificate number: 11 2325749
IECEx
IECEx SIR 10.0056X
Ex d IIC T6 Gb
Ex tb IIIC T85°C Db IP68
Ta = -40°C to +75°C
Special Conditions for Safe Use:
Use suitably certified and dimensioned cable entry device and/or plug. The
equipment shall be installed such that the supply cable is protected from
mechanical damage. The cable shall not be subjected to tension or torque. If the
cable is to be terminated within an explosive atmosphere, then appropriate
protection of the free end of the cable shall be provided.
Year of Construction
This information is contained within the serial number with the first four digits
representing the year and month in the YYMM format.
For European Community:
The PD663 must be installed in accordance with the
ATEX directive 94/9/EC and the product certificate Sira 10ATEX1116X.