Multi-Point Linearization (
Linear
)
Meters are set up at the factory for linear function with 2-point
linearization. Up to 32 linearization points can be selected under the
linear function.
The multi-point linearization can be used to linearize the
display for non-linear signals.
Low-Flow Cutoff (
CutofF
)
The low-flow cutoff feature allows the meter to be programmed so that
the often-unsteady output from a differential pressure transmitter, at low
flow rates, always displays zero on the meter.
The cutoff value may be programmed from 0 to 999999. The meter will
display zero below the cutoff value. Programming the cutoff value to zero
disables the cutoff feature.