Loop Leader PD6622/4 Loop-Powered Rate/Totalizer Instruction Manual
27
Alarm (
ALARM
)
Alarm outputs may be assigned to the rate, total, or grand total values, or the digital input. When assigned
to the rate, the alarm may be set as either a high alarm or a low alarm. Alarm actions (
AUTO
,
AUTO.MAN
,
LATCH
,
L-CLEAR
) determine how and when the alarm should be reset. They operate as follows:
Automatic (
AUTO
):
Alarm will reset automatically once the alarm condition has cleared.
Automatic/Manual (
AUTO.MAN
):
Alarm will reset automatically once the alarm condition has
cleared but can also be reset using the
Enter
button (or whichever function key is set to
acknowledge).
Latching (
LATCH
):
Alarm will
not
reset automatically even if the alarm condition is cleared. Press
the
Enter
button at any time to clear the alarm.
Latching w/ Clear (
L-CLEAR
):
Alarm will
not
reset automatically. Press the
Enter
button
once
the alarm condition has cleared
to reset the alarm.
If the alarm is set to rate, a set and reset point must be programmed. The set point is the display value at
which the alarm will turn on and the reset point is the display value at which the alarm will turn off. If the
set point is lower than the reset point, the alarm will be a low alarm; if the set point is higher than the reset
point, the alarm will be a high alarm. If the alarm is set to total or grand total, only a set point needs to be
programmed. The digital input alarm will trigger whenever the digital input is triggered.
For all alarms, a delay before the alarm is turned on or off may be set, as well as a failsafe feature which
will inverse the on/off programming.
Alarm states will be displayed on the meter even if no relay output is physically connected. The alarm in-
dicator (!) will display as well as optional red LED backlight, flashing rate, total, or grand total value (rate,
total, or grand total alarms only), and a programmable alarm message.
RLY 1
ALARM
ALARM
D.INPUT
ALARM
ACTION
ACTN
AUTO
ACTN
AUTO.MAN
ACTN
LATCH
ACTN
L-CLEAR
SET
+00,040.00
SET
GAL
Flashes
Units
ALARM
RESET
ALARM
SET
RESET
+00,030.00
ALARM
DELAY
DELAY
ON
TIME
0000 SEC
DELAY
OFF
TIME
0000 SEC
ALARM
FAILSAFE
Rate, Total, GTotal Alarm Only
FSAFE
OFF
ALARM
DISPLAY
RED
ON
FLASH
ON
ALARM
GTOTAL
Rate Alarm Only
Rate, Total, Gr.
ALARM
RATE
ALARM
TOTAL
MSG
ON
MSG
ALARM 1
Total Alarm Only