Loop Leader PD6622/4 Loop-Powered Rate/Totalizer Instruction Manual
23
Pulse (
PULSE
)
Pulse outputs may be assigned to output the rate, total, or grand total at a programmable factor. The fac-
tor determines the number of pulses per second which should be generated per unit of measure. For ex-
ample, if the meter display shows 100 gallons and the factor is set to 2, the number of pulses generated
per second would be 200. The maximum frequency is 250 Hz.
Setting output 2 to quadrature will duplicate the other open collector output, but lag by 90 degrees out of
phase. The other output should be programmed as desired for the quadrature output function, and must
be a pulse (
PULSE
) output selection. The quadrature maximum frequency for both outputs is 125 Hz.
The
TEST
option will output a fixed number of pulses per second based on the
FREQ
value entered.
OUT 1
PULSE
PULSE
TEST
PULSE
QUAD
*Available
for output
2 only.
*
FACTR
GAL/S
Flashes
Units
FACTR
+0,001.000
FREQ
100.0
PULSE
RATE
PULSE
TOTAL
PULSE
GTOTAL