Loop Leader PD6622/4 Loop-Powered Rate/Totalizer Instruction Manual
7
Safety Information
CAUTION
:
Read complete in-
structions prior to installation
and operation of the meter.
WARNING
:
Risk of electric
shock or personal injury.
Warning!
Hazardous voltages exist within enclosure.
Installation and service should be performed
only by trained service personnel.
Installation
There is no need to remove the meter from its case to complete the installation, wiring, and setup of
the meter for most applications.
Unpacking
Remove the meter from box. Inspect the packaging and contents for damage. Report damages, if
any, to the carrier.
If any part is missing or the meter malfunctions, please contact your supplier or the factory for assis-
tance.
Panel Mounting Instructions
Prepare a standard 1/8 DIN panel cutout
– 3.622" x 1.772" (92 mm x 45 mm). Refer to Figure 1 be-
low, for more details.
Clearance: allow at least 4.0" (102 mm) behind the panel for wiring.
Panel thickness: 0.04" - 0.25" (1.0 mm - 6.4 mm).
Recommended minimum panel thickness to maintain Type 4X rating: 0.06" (1.5 mm) steel panel,
0.16" (4.1 mm) plastic panel.
Remove the two mounting brackets provided with the meter (back-off the two screws so that there is ¼"
(6.4 mm) or less through the bracket. Slide the bracket toward the front of the case and remove).
Insert meter into the panel cutout.
Install mounting brackets and tighten the screws against the panel. To achieve a proper seal, tighten
the mounting bracket screws evenly until meter is snug to the panel along its short side. DO NOT
OVER TIGHTEN, as the rear of the panel may be damaged.
Figure 1. 1/8 DIN Panel Cutout Dimensions and Panel Mounting Details
!