PD6830X Explosion-Proof Modbus Scanners
Instruction Manual
58
Parameter
PD6830X
Description/Comment
Serial Communications
Scanner ID
246
Must be Unique on the Network
Baud
4800 bps
Must Match All Network Devices
Transmit Time Delay
50 ms
Parity
None 1
Must Match All Network Devices
Setup
Display
Top Display
PV
Show Only PVs
Bottom Display
Tag & Units
Show Tag and Units for Each PV
PV Setup
PV 1
Identical for PV1, 4, 7, and 10
Format
Top Display
Tag
T1 LVL
Indicates Tank 1 Level
Units
FEET
Display Decimal Point
2
Scale
Scaling for Level
Input 1
00000
Display 1
0.00
Input 2
12000
x1000 inch
Display 2
10.00
Feet
PV 2
Identical for PV2, 5, 8, and 11
Format
Top Display
Tag
T1 INT
Indicates Tank 1 Interface Registers
Units
FEET
Display Decimal Point
2
Scale
Scaling for Interface Registers
Input 1
00000
Display 1
0.00
Input 2
12000
x1000 inch
Display 2
10.00
Feet
PV 3
Identical for PV3, 6, 9, and 12
Format
Top Display
Tag
T1TEMP
T1 Indicates Tank 1 Average Temperature
Units
°F
Display Decimal Point
1
Scale
Scaling for Temperature Registers
Input 1
00000
Display 1
0.0
Input 2
10000
x10,000 deg F
Display 2
10.0
Deg F