PD6830X Explosion-Proof Modbus Scanners
Instruction Manual
60
The following table shows the PD6830X setup to work with two Modbus flowmeters.
Parameter
PD6830X
Description/Comment
Mode
Snooper
PV1
Enable
PV1 Slave ID
100
Flow Meter 1 Address
Function Code
03
Register PV1
40001
Flow Meter 1 Rate
Data Type
Long integer Binary,
Byte Order
1234
PV2
Enable
PV2 Slave ID
200
Flow Mater 2 Address
Function Code
03
Register PV2
40001
Flow Meter 2 Rate
Data Type
Long integer Binary,
Byte Order
1234
Snooper Mode Response Time
2.0 seconds
Default Value
Serial Communications
Scanner ID
246
Must be Unique on the Network
Baud
4600 bps
Must Match All Network Devices
Transmit Time Delay
50 ms
Parity
None, 1 Stop Bit
Must Match All Network Devices
Setup
Display
Top Display
PV, Tag, & Units
Show PV, Tag, and Units for Each Top PV
Bottom Display
PV, Tag, & Units
Show PV, Tag, and Units for Each Bottom PV
PV Setup
PV 1
Format
Top Display
Show PV 1 (Flow Meter 1 Rate) on Bottom Display
Tag
RATE 1
Indicates Flow Meter 1 Rate
Units
GPM
Indicates Gallons Per Minute
Display Decimal Point
1
Scale
Scaling for Rate
Input 1
00000
Display 1
0.0
Input 2
50000
Display 2
5000.0
PV 2
Format
Bottom Display
Show PV 2 (Flow Meter 2 Rate) on Bottom Display
Tag
RATE 2
Indicates Flow Meter 2 Rate
Units
GPM
Indicates Gallons Per Minute
Display Decimal Point
1
Scale
Scaling for Rate
Input 1
00000
Display 1
0.0
Input 2
50000
Display 2
5000.0