PD6830X Explosion-Proof Modbus Scanners
Instruction Manual
56
The following table shows the PD6830X setup to work with the MTS LP-Series gauges.
Parameter
PD6830X
Description/Comment
Display
Mode
Master
PV1
Enable
PV1 Slave ID
1
Function Code
04
Register PV1
30001
Tank 1 Product Level
Data Type
Long integer Binary, Signed
Byte Order
1234
PV2
Enable
PV2 Slave ID
1
Function Code
04
Register PV2
30003
Tank 1 Interface
Data Type
Long integer Binary, Signed
Byte Order
1234
PV3
Enable
PV3 Slave ID
1
Function Code
04
Register PV3
30017
Tank 1 Average Temperature
Data Type
Long integer Binary, Signed
Byte Order
1234
PV4
Enable
PV4 Slave ID
2
Function Code
04
Register PV4
30001
Tank 2 Product Level
Data Type
Long integer Binary, Signed
Byte Order
1234
PV5
Enable
PV5 Slave ID
2
Function Code
04
Register PV5
30003
Tank 2 Interface
Data Type
Long integer Binary, Signed
Byte Order
1234
PV6
Enable
PV6 Slave ID
2
Function Code
04
Register PV6
30017
Tank 2 Average Temperature
Data Type
Long integer Binary, Signed
Byte Order
1234