  5 / 16 

d0.20 

Remaining run time 

Remaining run time display, it is for timing run control 

0.1Min 

d0.21 

Linear speed 

Show the line speed of DI5 high speed pulse sampling, 
according to the actual sample pulse number per minute 
and E0.07, calculate the line speed value. 

1m/Min 

d0.22 

Current power-on time 

Total time of current inverter power-on 

1Min 

d0.23 

Current run time 

Total time of current inverter run 

0.1Min 

d0.24 

HDI(DI5) impulse frequency 

HDI(DI5) high-speed impulse input frequency display, 
unit: 1Hz 

1Hz 

d0.25 

Communication set value 

Frequency, torque or other command values set by 
communication port 

0.01% 

d0.27 

Master frequency setting 
display 

Frequency set by F0.03 master frequency setting source 

0.01Hz 

d0.28 

Auxiliary frequency setting 
display 

Frequency set by F0.04 auxiliary frequency setting 
source 

0.01Hz 

d0.35 

Inverter status 

Display the running and standby etc status information 

d0.36 

Inverter type 

1:G type: Suitable for constant torque load;     
2:F type: Suitable for variable torque load (Fans, pumps 
load) 

d0.37 

AI1 voltage before correction  Input voltage value before linear correction of AI1 

0.01V 

F0 group    Basic function group 

Code 

Parameter name 

Setting range 

Factory 

setting 

Cha

nge 

F0.00  Motor control mode 

0:Vector control without PG         
2:V/F control 

 

F0.01  Keyboard set frequency 

0.00Hz to F0.19(Maximum frequency) 

50.00Hz 

 

F0.02  Frequency command 

resolution 

1: 0.1Hz                       
2: 0.01Hz 

 

F0.03  Frequency source master 

setting 

0: Keyboard set frequency (F0.01, UP/DOWN can be 
modified, power-down without memory) 
1: Keyboard set frequency (F0.01, UP/DOWN can be 
modified, power-down with memory) 
2: Analog AI1 setting;4: Panel potentiometer setting 
5:High-speed pulse setting; 
6: Multi-speed operation setting 
7: Simple PLC program setting; 
8: PID control setting; 
9:Remote communications setting 

 

F0.04  Frequency source 

auxiliary setting 

Same as F0.03 setting   

 

F0.05 

Reference object selection 
for frequency source 
auxiliary setting 

0. Relative to maximum frequency; 
1. Relative to master frequency source 1 
2. Relative to master frequency source 2 

 

F0.06  Frequency source 

auxiliary setting range 

0% to 150% 

100% 

 

F0.07  Frequency superimposed 

selection 

Units digit: Frequency source selection; 
Tens digit: Arithmetic relationship of master and 
auxiliary for frequency source 

00 

 

F0.08 

Frequency source offset 
frequency when 
superimposing 

0.00Hz to F0.19(Maximum frequency) 

0.00Hz 

 

F0.09 

Shutdown memory 
selection for digital set 
frequency 

0: W/O memory;             
1: With memory 

 

F0.10  UP/DOWN standard 

0: Running frequency ;         
1: Set frequency 

 

F0.11  Command source 

selection 

0. Keyboard control (LED off);     
1. Terminal block control (LED on) 
2. Communications command control (LED flashes) 
3. Keyboard  Communications command 
control   
4. Keyboard  Communications command 
 Terminal block control 

 

F0.12  Binding frequency source 

for command source 

Units digit: Keyboard command binding frequency 
source selection   
0:Not binded;   
1: Keyboard set frequency; 
2:AI1 setting;                     
4:Panel potentiometer setting; 
5:High-speed pulse setting;     
6:Multi-speed setting 
7:Simple PLC setting;             
8:PID setting; 
9:Communications reference 
Tens digit: Terminal block command binding 
frequency source selection (0 to 9, same as units 
digit) 
Hundreds digit: Communication command binding 
frequency source selection (0 to 9, same as units 
digit) 

000 

 

F0.13  Acceleration time 1 

0.0s to 6500s 

Depend 

on type 

 

F0.14  Deceleration time 1 

0.0s to 6500s 

Depend 

on type 

 

F0.15  Ac/Deceleration time unit 

0:1s;             
1:0.1s;                 
2:0.01s 

 

F0.16  Ac/deceleration time 

reference frequency 

0:F0.19(Maximum frequency)           
1:Set frequency;     
2:100Hz 

 

F0.17 

Carrier frequency 
adjustment as per 
temperature 

0:NO ;             
1: YES 

 

F0.18  Carrier Frequency 

0.5kHz to 16.0kHz 

Depend 

on type 

 

F0.19  Maximum output 

frequency 

50.00Hz to 320.00Hz 

50.00Hz 

 

F0.20  Upper limit frequency 

source 

0:F0.21 setting;   
1:AI1 setting; 
3:Panel potentiometer setting; 
4: High-speed pulse setting;   
5: Communications reference 

 

F0.21  Upper limit frequency 

F0.23 (Lower limit frequency) to F0.19 (Maximum 
frequency) 

50.00Hz 

 

F0.22  Upper limit frequency 

0.00Hz to F0.19 (Maximum frequency) 

0.00Hz 

 

Summary of Contents for PI500 011G2

Page 1: ...maintenance care For any problem within the warranty period please fill out the warranty card and fix it to our authorized dealer 2 Instructions on nameplate Model designation POWTRAN Inverter PI 500...

Page 2: ...ops LOCAL REMOTE Command indicator light That is the indicator for keyboard operation terminal operation and remote operation Communication contral ON terminal control working status OFF keyboard cont...

Page 3: ...range 0m to 6500m Running Input signal DI input terminal 6 digital input terminals DI5 for high speed pulse input 0 to 100 kHz square wave AI1 analog input 1 analog input terminals respectively for o...

Page 4: ...make sure that there is no mistake before power can be turned on 7 Parameter list In PI500A series frequency inverters some parameters are manufacturer reserved and their serial numbers are not liste...

Page 5: ...ting 0 Relative to maximum frequency 1 Relative to master frequency source 1 2 Relative to master frequency source 2 0 F0 06 Frequency source auxiliary setting range 0 to 150 100 F0 07 Frequency super...

Page 6: ...ed to switch between two frequency sources 19 UP DOWN setting Terminal keyboard When the frequency reference is the digital frequency this terminal is used to clear the changed frequency value by term...

Page 7: ...ad warning is exceeded For motor overload parameter setting refer to function codes F8 02 F8 04 7 Frequency inverter overload forecasting alarm The output signal ON 10 seconds before the overload prot...

Page 8: ...git SPA Ten thousands digit Relay 2 00000 F2 16 DA1 zero bias coefficient 100 0 to 100 0 0 0 F2 17 DA1 gain 10 00 to 10 00 1 00 F3 group Start stop control parameters group Code Parameter name Setting...

Page 9: ...verter module radiator temperature 0 0 to 100 0 F6 07 Total run time 0h to 65535h F6 08 Total power on time 0h to 65535h F6 09 Total power consumption 0 to 65535kWh F6 10 Product series number Frequen...

Page 10: ...0 to 300 0 Rated motor current 0 0 F7 40 Module temperature arrival 0 to 100 75 F7 41 Cooling fan control 0 Fan running only when running 1 Fan always running 0 F7 42 Timing function selection 0 Inval...

Page 11: ...depth 0 E0 group Pendulum frequency fixed length and counting parameter array Code Parameter name Setting range Factory setting Chan ge E0 00 Swing setting mode 0 Relative to center frequency 1 Relat...

Page 12: ...h 0 0s h E1 49 15 stage ac deceleration time selection Same as E1 19 0 E1 50 Simple PLC run time unit 0 S seconds 1 H hours 0 E1 51 Multi stage command 0 reference manner 0 Function code E1 00 referen...

Page 13: ...e Setting range Factory setting Cha nge y0 00 Parameter initialization 0 Nno operation 1 Restore default parameter values not including motor parameters 2 Clear history 3 Restore default parameter val...

Page 14: ...ppens 2 The control mode is vector and without identification of parameters 3 The deceleration time is too short 4 The voltage is low 5 Suddenly increase the load in the process of deceleration 6 Didn...

Page 15: ...2 Replace hall device 21 Err 21 Motor parameter auto tuning fault 1 The motor parameters was not set according to the nameplate 2 The identification process of parameter is timeout 1 correctly set mot...

Page 16: ...yboard compartment Dimension drawing of keyboard compartment dimension unit mm PI500 pI500A keyboard installation opening dimension drawing Mounting panel Opening size of external mounting panel Openi...

Reviews: