F9 group    Communication parameter set 

Code 

Parameter name 

Setting range 

Factory 

setting 

Chan

ge 

F9.00 

Baud rate 

Units digit:Modbus 
2:1200BPS; 
3:2400BPS; 
4:4800BPS; 
5:9600BPS 
6:19200BPS; 
7:38400BPS; 
8:57600BPS; 
9:115200BPS 
Tens digit:Reserved ; 
Hundreds digit: Reserved; 
Thousands digit:Reserved 

6005 

 

F9.01 

Data format 

0:No parity(8-N-2); 
1:Even parity(8-E-1)   
2:Odd parity(8-O-1)     
3:No parity(8-N-1) 

 

F9.02 

This unit address 

1 to 250,0 for broadcast address 

 

F9.03 

Response delay 

0ms to 20ms 

2ms 

 

F9.04 

Communication timeout time  0.0(Invalid);0.1 to 60.0s 

0.0 

 

F9.05 

Data transfer format selection 

Units digit:Modbus 
0:Non-standard MODBUS protocol;1:Standard 
MODBUS protocol 
Tens digit:Profibus-DP 
0:PPO1 format;1:PPO2 format;2:PPO3 
format;3:PPO5 format 

31 

 

F9.06 

Communication read current 
resolution 

0:0.01A ;1:0.1A 

 

F9.07 

Communication card type 

0:Modbus communication card 

 

Fb group    Control optimization parameter group 

Code 

Parameter name 

Setting range 

Factory 

setting 

Chan

ge 

Fb.00 

Fast current limiting manner 

0:Disable;                         
1: Enable 

 

Fb.01 

Undervoltage point setting 

50.0% to 140.0% 

100.0% 

 

Fb.02 

Overvoltage point setting 

200.0 to 2500.0V 

 

Fb.03 

Deadband compensation 
mode selection 

0:No compensation;   
1:Compensation mode 1; 
2:Compensation mode 2 

 

Fb.04 

Current detection compensation 0 to 100 

 

Fb.05 

Vector optimization without 
PG mode selection 

0:No optimization;     
1:Optimization mode 1; 
2:Optimization mode 2 

 

Fb.06 

Upper limiting frequency for 
DPWM switching 

0.00 to 15.00Hz 

12.00Hz 

 

Fb.07 

PWM modulation method 

0:Asynchronous;                   
1:Synchronous 

 

Fb.08 

PWM modulation manner 

0:Invalid   
1 to 10:PWM carrier frequency random depth 

 

E0 group    Pendulum frequency, fixed length and counting parameter array 

Code 

Parameter name 

Setting range 

Factory 

setting 

Chan

ge 

E0.00 

Swing setting mode 

0:Relative to center frequency; 
1:Relative to maximum requency 

 

E0.01 

Wobbulate range 

0.0% to 100.0% 

0.0% 

 

E0.02 

Sudden jump frequency range 

0.0% to 50.0% 

0.0% 

 

E0.03 

Wobbulate circle 

0.1s to 3000.0s 

10.0s 

 

E0.04 

Triangle wave rise time coefficient  0.1% to 100.0% 

50.0% 

 

E0.05 

Set length 

0m to 65535m 

1000m 

 

E0.06 

Actual length 

0m to 65535m 

0m 

 

E0.07 

Pulse per meter 

0.1 to 6553.5 

100.0 

 

E0.08 

Set count value 

1 to 65535 

1000 

 

E0.09 

Specified count value 

1 to 65535   

1000 

 

E1 group    Multi-section instruction and simple PLC parameter set 

Code 

Parameter name 

Setting range 

Factory 

setting 

Chan

ge 

E1.00 

0-stage speed setting 0X 

-100.0% to 100.0% 

0.0% 

 

E1.01 

1-stage speed setting 1X 

-100.0% to 100.0% 

0.0% 

 

E1.02 

2-stage speed setting 2X 

-100.0% to 100.0% 

0.0% 

 

E1.03 

3-stage speed setting 3X 

-100.0% to 100.0% 

0.0% 

 

E1.04 

4-stage speed setting 4X 

-100.0% to 100.0% 

0.0% 

 

E1.05 

5-stage speed setting 5X 

-100.0% to 100.0% 

0.0% 

 

E1.06 

6-stage speed setting 6X 

-100.0% to 100.0% 

0.0% 

 

E1.07 

7-stage speed setting 7X 

-100.0% to 100.0% 

0.0% 

 

E1.08 

8-stage speed setting 8X 

-100.0% to 100.0% 

0.0% 

 

E1.09 

9-stage speed setting 9X 

-100.0% to 100.0% 

0.0% 

 

E1.10 

10-stage speed setting 10X 

-100.0% to 100.0% 

0.0% 

 

E1.11 

11-stage speed setting 11X 

-100.0% to 100.0% 

0.0% 

 

E1.12 

12-stage speed setting 12X 

-100.0% to 100.0% 

0.0% 

 

E1.13 

13-stage speed setting 13X 

-100.0% to 100.0% 

0.0% 

 

E1.14 

14-stage speed setting 14X 

-100.0% to 100.0% 

0.0% 

 

E1.15 

15-stage speed setting 15X 

-100.0% to 100.0% 

0.0% 

 

E1.16 

Simple PLC running mode 

0: Stop after single running 
1: Hold final value after single running 
2: Circulating 

 

E1.17 

Simple PLC power-down memory 
selection 

Units digit: power-down memory 
selection 
0: Power-down without memory 
1: Power-down with memory 

11 

 

Summary of Contents for PI500 011G2

Page 1: ...maintenance care For any problem within the warranty period please fill out the warranty card and fix it to our authorized dealer 2 Instructions on nameplate Model designation POWTRAN Inverter PI 500...

Page 2: ...ops LOCAL REMOTE Command indicator light That is the indicator for keyboard operation terminal operation and remote operation Communication contral ON terminal control working status OFF keyboard cont...

Page 3: ...range 0m to 6500m Running Input signal DI input terminal 6 digital input terminals DI5 for high speed pulse input 0 to 100 kHz square wave AI1 analog input 1 analog input terminals respectively for o...

Page 4: ...make sure that there is no mistake before power can be turned on 7 Parameter list In PI500A series frequency inverters some parameters are manufacturer reserved and their serial numbers are not liste...

Page 5: ...ting 0 Relative to maximum frequency 1 Relative to master frequency source 1 2 Relative to master frequency source 2 0 F0 06 Frequency source auxiliary setting range 0 to 150 100 F0 07 Frequency super...

Page 6: ...ed to switch between two frequency sources 19 UP DOWN setting Terminal keyboard When the frequency reference is the digital frequency this terminal is used to clear the changed frequency value by term...

Page 7: ...ad warning is exceeded For motor overload parameter setting refer to function codes F8 02 F8 04 7 Frequency inverter overload forecasting alarm The output signal ON 10 seconds before the overload prot...

Page 8: ...git SPA Ten thousands digit Relay 2 00000 F2 16 DA1 zero bias coefficient 100 0 to 100 0 0 0 F2 17 DA1 gain 10 00 to 10 00 1 00 F3 group Start stop control parameters group Code Parameter name Setting...

Page 9: ...verter module radiator temperature 0 0 to 100 0 F6 07 Total run time 0h to 65535h F6 08 Total power on time 0h to 65535h F6 09 Total power consumption 0 to 65535kWh F6 10 Product series number Frequen...

Page 10: ...0 to 300 0 Rated motor current 0 0 F7 40 Module temperature arrival 0 to 100 75 F7 41 Cooling fan control 0 Fan running only when running 1 Fan always running 0 F7 42 Timing function selection 0 Inval...

Page 11: ...depth 0 E0 group Pendulum frequency fixed length and counting parameter array Code Parameter name Setting range Factory setting Chan ge E0 00 Swing setting mode 0 Relative to center frequency 1 Relat...

Page 12: ...h 0 0s h E1 49 15 stage ac deceleration time selection Same as E1 19 0 E1 50 Simple PLC run time unit 0 S seconds 1 H hours 0 E1 51 Multi stage command 0 reference manner 0 Function code E1 00 referen...

Page 13: ...e Setting range Factory setting Cha nge y0 00 Parameter initialization 0 Nno operation 1 Restore default parameter values not including motor parameters 2 Clear history 3 Restore default parameter val...

Page 14: ...ppens 2 The control mode is vector and without identification of parameters 3 The deceleration time is too short 4 The voltage is low 5 Suddenly increase the load in the process of deceleration 6 Didn...

Page 15: ...2 Replace hall device 21 Err 21 Motor parameter auto tuning fault 1 The motor parameters was not set according to the nameplate 2 The identification process of parameter is timeout 1 correctly set mot...

Page 16: ...yboard compartment Dimension drawing of keyboard compartment dimension unit mm PI500 pI500A keyboard installation opening dimension drawing Mounting panel Opening size of external mounting panel Openi...