background image

  14 / 16 

last) fault 

y1.07 

Output terminal status of the third(at 
last) fault 

● 

y1.08 

Reserved 

 

 

 

y1.09 

Power-on time of the third(at last) 
fault 

● 

y1.10 

Running time of the third(at last) fault 

● 

y1.13 

Reserve 

● 

y1.14 

Reserve 

● 

y1.15 

Frequency of the second fault 

● 

y1.16 

Current of the second fault 

● 

y1.17 

Bus voltage of the second fault 

● 

y1.19 

Input terminal status of the second 
fault 

● 

y1.20 

Output terminal status of the second 
fault 

● 

y1.23 

Reserved 

● 

y1.24 

Power-on time of the second fault 

● 

y1.25 

Running time of the second fault 

● 

y1.26 

Reserve 

● 

y1.27 

Reserve 

● 

y1.29 

Frequency of the first fault 

● 

y1.30 

Running time at first failure 

● 

8. 

 

Fault alarm and countermeasures 

PI500A can provide effective protection when the equipment performance is played fully. In case of 

abnormal fault, the protection function will be invoked, the inverter will stop output, and the faulty relay 
contact of the inverter will start, and the fault code will be displayed on the display panel of the inverter. Before 
consulting the service department, user can perform self-check , analyze the fault cause and find out the 
solution according to the instructions of this chapter. If the fault is caused by the reasons as described in the 
dotted frame, please consult the agents of inverter or directly contact with our company. 

No.  Fault ID  Failure type 

Possible causes 

Solutions 

Err.01 

Inverter unit 
protection 

1.The short circuit of inverter output 
happens 
2.The wiring    for the motor and the 
inverter is too long 
3.Module overheating 
4.The internal wiring of inverter is 
loose 
5.The main control panel is abnormal 
6.The drive panel is abnormal. 
7.The inverter module is abnormal 

1.Eliminate peripheral faults 
2.Additionally install the reactor or 
the output filter 
3.Check the air duct is blocked or 
not and the fan is working normally 
or not, and eliminate problems 
4.Correctly plug all cables 
5.Seek for technical support 

Err.02 

Acceleration 
overcurrent 

1.The acceleration time is too short 
2.Manual torque boost or V/F curve is 
not suitable 
3.The voltage is low 
4.The short-circuit or earthing of 
inverter output happens 
5.The control mode is vector and 
without identification of parameters 
6.The motor that is rotating is started 
unexpectedly. 
7.Suddenly increase the load in the 
process of acceleration. 
8.The type selection of inverter is 
small 

1.Increase acceleration time 
2.Adjust manual torque boost or 
V/F curve 
3.Set the voltage to the normal 
range 
4.Eliminate peripheral faults 
5.Perform identification for the 
motor parameters 
6.Select Speed Tracking Start or 
restart after stopping the motor. 
7.Cancel the sudden load 
8.Choose the inverter with large 
power level 

Err.03 

Deceleration 
overcurrent 

1.The short-circuit or earthing of 
inverter output happens 
2.The control mode is vector and 
without identification of parameters 
3.The deceleration time is too short 
4.The voltage is low 
5.Suddenly increase the load in the 
process of deceleration. 
6.Didn't install braking unit and 
braking resistor 

1.Eliminate peripheral faults 
2.Perform identification for the 
motor parameters 
3.Increase the deceleration time 
4.Set the voltage to the normal range 
5.Cancel the sudden load 
6.Install braking unit and brake 
resistor 

Err.04 

Constant speed 
overcurrent 

1.The short-circuit or earthing of 
inverter output happens 
2.The control mode is vector and 
without identification of parameters 
3.The voltage is low 
4.Whether suddenly increase the load 
when running 
5.The type selection of inverter is 
small 

1.Eliminate peripheral faults 
2.Perform identification for the 
motor parameters 
3.Set the voltage to the normal range 
4.Cancel the sudden load 
5.Choose the inverter with large 
power level 

Err.05 

Acceleration 
overvoltage 

1.Didn't install braking unit and 
braking resistor 
2.The input voltage is high 
3.There is external force to drag the 
motor to run when accelerating. 
4.The acceleration time is too short 

1.Install braking unit and brake 
resistor 
2.Set the voltage to the normal range 
3.Cancel the external force or 
install braking resistor. 
4.Increase acceleration time 

Err.06 

Deceleration 
overvoltage 

1.The input voltage is high 
2.There is external force to drag the 
motor to run when decelerating. 
3.The deceleration time is too short 
4.Didn't install braking unit and 
braking resistor 

1.Set the voltage to the normal range 
2.Cancel the external force or 
install braking resistor. 
3.Increase the deceleration time 
4.Install braking unit and brake 
resistor 

Err.07 

Constant    speed 
overvoltage 

1.There is external force to drag the 
motor to run when running 
2.The input voltage is high 

1.Cancel the external force or 
install braking resistor. 
2.Set the voltage to the normal range 

Err.08 

Control power 
failure 

The range of input voltage is not 
within the specification 

Adjust the voltage to the range of 
the requirements of specification 

Err.09 

Under voltage 
fault 

1.The momentary power cut 
2.The inverter's input voltage is not 
within the specification 
3.The bus voltage is not normal 
4.The rectifier bridge and buffer 
resistance are abnormal 
5.The drive panel is abnormal. 
6.The control panel is abnormal 

1.Reset fault 
2.Adjust the voltage to the normal 
range 
3.Seek for technical support 

10 

Err.10 

Inverter 
overload 

1.The type selection of inverter is 
small 
2.whether the load is too large or the 
motor stall occurs 

1.Choose the inverter with large 
power level 
2.Reduce the load and check the 
motor and its mechanical 
conditions 

11 

Err.11 

Motor 
Overload 

1. power grid voltage is too low 
2.whether the setting motor protection 
parameters (F8.03) is appropriate or 

1.Check the power grid voltage 
2.Correctly set this parameter. 
3.Reduce the load and check the 

Summary of Contents for PI500 011G2

Page 1: ...maintenance care For any problem within the warranty period please fill out the warranty card and fix it to our authorized dealer 2 Instructions on nameplate Model designation POWTRAN Inverter PI 500...

Page 2: ...ops LOCAL REMOTE Command indicator light That is the indicator for keyboard operation terminal operation and remote operation Communication contral ON terminal control working status OFF keyboard cont...

Page 3: ...range 0m to 6500m Running Input signal DI input terminal 6 digital input terminals DI5 for high speed pulse input 0 to 100 kHz square wave AI1 analog input 1 analog input terminals respectively for o...

Page 4: ...make sure that there is no mistake before power can be turned on 7 Parameter list In PI500A series frequency inverters some parameters are manufacturer reserved and their serial numbers are not liste...

Page 5: ...ting 0 Relative to maximum frequency 1 Relative to master frequency source 1 2 Relative to master frequency source 2 0 F0 06 Frequency source auxiliary setting range 0 to 150 100 F0 07 Frequency super...

Page 6: ...ed to switch between two frequency sources 19 UP DOWN setting Terminal keyboard When the frequency reference is the digital frequency this terminal is used to clear the changed frequency value by term...

Page 7: ...ad warning is exceeded For motor overload parameter setting refer to function codes F8 02 F8 04 7 Frequency inverter overload forecasting alarm The output signal ON 10 seconds before the overload prot...

Page 8: ...git SPA Ten thousands digit Relay 2 00000 F2 16 DA1 zero bias coefficient 100 0 to 100 0 0 0 F2 17 DA1 gain 10 00 to 10 00 1 00 F3 group Start stop control parameters group Code Parameter name Setting...

Page 9: ...verter module radiator temperature 0 0 to 100 0 F6 07 Total run time 0h to 65535h F6 08 Total power on time 0h to 65535h F6 09 Total power consumption 0 to 65535kWh F6 10 Product series number Frequen...

Page 10: ...0 to 300 0 Rated motor current 0 0 F7 40 Module temperature arrival 0 to 100 75 F7 41 Cooling fan control 0 Fan running only when running 1 Fan always running 0 F7 42 Timing function selection 0 Inval...

Page 11: ...depth 0 E0 group Pendulum frequency fixed length and counting parameter array Code Parameter name Setting range Factory setting Chan ge E0 00 Swing setting mode 0 Relative to center frequency 1 Relat...

Page 12: ...h 0 0s h E1 49 15 stage ac deceleration time selection Same as E1 19 0 E1 50 Simple PLC run time unit 0 S seconds 1 H hours 0 E1 51 Multi stage command 0 reference manner 0 Function code E1 00 referen...

Page 13: ...e Setting range Factory setting Cha nge y0 00 Parameter initialization 0 Nno operation 1 Restore default parameter values not including motor parameters 2 Clear history 3 Restore default parameter val...

Page 14: ...ppens 2 The control mode is vector and without identification of parameters 3 The deceleration time is too short 4 The voltage is low 5 Suddenly increase the load in the process of deceleration 6 Didn...

Page 15: ...2 Replace hall device 21 Err 21 Motor parameter auto tuning fault 1 The motor parameters was not set according to the nameplate 2 The identification process of parameter is timeout 1 correctly set mot...

Page 16: ...yboard compartment Dimension drawing of keyboard compartment dimension unit mm PI500 pI500A keyboard installation opening dimension drawing Mounting panel Opening size of external mounting panel Openi...

Reviews: