13 / 16
E2.24 PID initial value hold time
0.00s to 360.00s
0.00s
☆
E2.25
Maximum deviation of twice
outputs(Forward)
0.00% to 100.00%
1.00%
☆
E2.26
Maximum deviation of twice
outputs(Backward)
0.00% to 100.00%
1.00%
☆
E2.27 Computing status after PID stop
0: Stop without computing;
1: Stop with computing
1
☆
E2.29
PID automatic decrease frequency
selection
0:Invalid;
1:Valid
1
☆
E2.30 PID stop frequency
0.00Hz to maximum frequency(F0.19)
25
☆
E2.31 PID checking time
0s to 3600s
10
☆
E2.32 PID checking times
10 to 500
20
☆
b0 group Motor parameters
Code
Parameter name
Setting range
Factory
setting
Cha
nge
b0.00
Motor type selection
0: General asynchronous motor
1: Asynchronous inverter motor
0
★
b0.01
Rated power
0.1kW to 1000.0kW
Depends on
models
★
b0.02
Rated voltage
1V to 2000V
Depends on
models
★
b0.03
Rated current
0.01A to 655.35A (Inverter power
≦
55kW)
0.1A to 6553.5A (Inverter rate> 55kW)
Depends on
models
★
b0.04
Rated frequency
0.01Hz to F0.19 (Maximum frequency)
Depends on
models
★
b0.05
Rated speed
1rpm to 36000rpm
Depends on
models
★
b0.06
Asynchronous motor
stator resistance
0.001Ω to 65.535Ω (Inverter power <= 55kW)
0.0001Ω to 6.5535Ω (Inverter power> 55kW)
Motor
parameters
★
b0.07
Asynchronous motor
rotor resistance
0.001Ω to 65.535Ω (Inverter power <= 55kW)
0.0001Ω to 6.5535Ω (Inverter power> 55kW)
Motor
parameters
★
b0.08
Asynchronous motor
leakage inductance
0.01mH to 655.35mH (Inverter power <= 55kW)
0.001mH to 65.535mH (Inverter power> 55kW)
Motor
parameters
★
b0.09
Asynchronous motor
mutUal inductance
0.1mH to 6553.5mH (Inverter power <= 55kW)
0.01mH to 655.35mH (Inverter power> 55kW)
Motor
parameters
★
b0.10
Asynchronous motor
no-load current
0.01A to b0.03 (Inverter power <= 55kW)
0.1A to b0.03 (Inverter power> 55kW)
Motor
parameters
★
b0.27
Motor parameter
auto tunning
0: No operation
1: Asynchronous motor parameters still auto tunning
2: Asynchronous motor parameters comprehensive auto
tunning
0
★
y0 group Function code management
Code
Parameter
name
Setting range
Factory
setting
Cha
nge
y0.00
Parameter
initialization
0:Nno operation
1: Restore default parameter values, not including motor
parameters
2: Clear history
3: Restore default parameter values, including motor parameters
4: Backup current user parameters
501: Restore from backup user parameters
0
★
y0.01
User password
0 to 65535
0
☆
y0.02
Function
parameter group
display selection
Units digit: d group display selection
0: Not displays 1: Displays
Tens digit: E group display selection(The same above)
Hundreds digit:b group display selection(The same above)
Thousands digit:y group display selection(The same above)
Tens thousands digit:L group display selection(The same above)
11111
★
y0.03
Personality
parameter group
display selection
Units digit:User’s customization parameter display selection
0:Not display 1:Display
Tens digit :User’s change parameter display selection
0:Not display 1:Display
00
☆
y0.04
Function code
modification
properties
0: Modifiable
1: Not modifiable
0
☆
y1 group Fault query parameter group
Code
Parameter name
Setting range
Factory
setting
Chan
ge
y1.00
Type of the first fault
0: No fault
1: Inverter unit protection
2: Acceleration overcurrent
3: Deceleration overcurrent
4: Constant speed overcurrent
5: Acceleration overvoltage
6: Deceleration overvoltage
7: Constant speed overvoltage
8: Control power failure
9: Undervoltage
10: Inverter overload
11: Motor overload
13: Output phase loss
14: Module overheating
15: External fault
16: Communication abnormal
17: Contactor abnormal
18: Current detection abnormal
19: Motor self-learning abnormal
21: Parameter read and write abnormal
22: Inverter hardware abnormal
23: Motor short to ground
26: Running time arrival
27: Custom fault 1
28: Custom fault 2
29; Power-on time arrival
31: PID feedback loss when running
40: Fast current limiting timeout
51:Initial position error
COF: communication failure
-
●
y1.01
Type of the second fault
-
●
y1.02
Type of the third(at last) fault
-
●
y1.03
Frequency of the third(at last) fault
-
-
●
y1.04
Current of the third(at last) fault
-
-
●
y1.05
Bus voltage of the third(at last) fault
-
-
●
y1.06
Input terminal status of the third(at
-
-
●