Powtran PI500 011G2 User Manual Download Page 6

  6 / 16 

offset 

F0.23  Lower limit frequency 

0.00Hz to F0.21(Lower limit frequency) 

0.00Hz 

 

F0.24  Running direction 

0: Same direction;         
1: Opposite direction 

 

F0.26  AI analog accuracy 

0: 0.01Hz;     
1: 0.05Hz;       
2: 0.1Hz;       
3: 0.5Hz 

 

F1 group    Input terminal parameter group 

Code 

Parameter name 

Setting range 

Factory 

setting 

Cha

nge 

F1.00 

DI1 terminal function selection 

0 to 51 

 

F1.01 

DI2 terminal function selection 

 

F1.02 

DI3 terminal function selection 

 

F1.03 

DI4 terminal function selection 

 

F1.04 

DI5 terminal function selection 

12 

 

F1.05 

DI6 terminal function selection 

13 

 

The functions of digital multi-functional input terminal DI1 to DI6 (DI5 can be used as high-speed pulse 

input terminal) can be set by parameter F1.00 to F1.05. The optional functions are shown in the following 
table: 

Set 

value 

Function 

Description 

No function 

The terminal for not use can be set to "no function" to prevent accidental 
operation. 

Forward run (FWD) 

External terminals are used to control the FWD run mode of inverter. 

Reverse run (REV) 

External terminals are used to control the REV run mode of inverter. 

Three-wire operation 
control 

This terminal is used to determine the inverter's three-wire control mode. 
For details, please refer to the instructions of function code F1.10 
("terminal command mode). 

Forward JOG(FJOG) 

FJOG means Forward JOG running, RJOG means Reverse JOG running. 
For Jog running frequency and Jog Ac/deceleration time, please refer to 
the description of the function code F7.00, F7.01, F7.02. 

Reverse JOG(RJOG) 

Terminal UP 

Modify frequency increment/decrement command when the frequency is 
referenced by external terminal. Adjust up/down the set frequency when 
the digital setting is selected as the frequency source. 

Terminal DOWN 

Free stop 

The inverter output is blocked, at the time, the parking process of motor is 
not controlled by the inverter. This way is same as the principle of free 
stop described in F3.07. 

Fault reset (RESET) 

The function make use of terminal for fault reset. It has same function 
with RESET key on the keyboard. This function can be used to realize 
remote fault reset. 

10 

Run pausing 

The inverter slows down and stops, but all operating parameters are 
memorized. Such as PLC parameters, wobbulate frequency parameters, 
and PID parameters. This terminal signal disappears, the inverter reverts 
to the previous state of running before parking. 

11 

External fault normally 
open input 

When the signal is sent to the inverter, the inverter reports fault Err.15, 
and performs troubleshooting according to fault protection action (For 
details, please refer to the function code F8.17). 

12 

Multi-speed terminal 1 

The setting of 16 stage speed or 16 kinds of other command can be 
achieved through the 16 states of the four terminals.For details, see Table 

13 

Multi-speed terminal 2 

14 

Multi-speed terminal 3 

15 

Multi-speed terminal 4 

16 

Ac/deceleration time 
selection terminal 1 

The selection of 4 ac/deceleration times can be achieved through the 4 
states of the two terminals. For details, see Table 2 

17 

Ac/deceleration time 
selection terminal 2 

18 

Frequency source 
switching 

Used to switch between different frequency sources. 
According to frequency source selection function code (F0.07) settings, 
the terminal is used to switch between two frequency sources. 

19 

UP/DOWN setting 
(Terminal, keyboard) 

When the frequency reference is the digital frequency, this terminal is 
used to clear the changed frequency value by terminal UP/DOWN or 
keyboard UP/DOWN, so that the reference frequency can recover to the 
set value of F0.01. 

20 

Run command switch 
terminal 1 

When the command source is set to the terminal control (F0.11 = 1), the 
terminal can be used to switch between terminal control and keyboard 
control. 
When the command source is set to the communication control (F0.11 = 
2), the terminal can be used to switch between communication control and 
keyboard control. 

21 

Ac/deceleration 
prohibited 

Ensure the inverter is free from external signals affect (Except for 
shutdown command), maintain current output frequency. 

22 

PID pause 

PID is temporarily disabled, the inverter maintains current output 
frequency, no longer performs PID adjustment of frequency source. 

23 

PLC status reset 

When PLC pauses and runs again, this terminal is used to reset the 
inverter to the initial state of simple PLC. 

24 

Wobbulate pause 

When the inverter outputs at center frequency. Wobbulate will pause 

25 

Counter input 

Input terminal of the count pulse 

26 

Counter reset 

Clear counter status 

27 

Length count input 

Input terminal of the length count. 

28 

Length reset 

Clear length 

30 

High-speed pulse input 
(Only valid for DI5 ) 

DI5 is used as pulse input terminal. 

32 

Immediately DC 
braking 

If the terminal is active, the inverter switches directly to DC braking 
status 

33 

External fault normally 
closed input 

When the signal of external fault normally closed input is inputted into 
the inverter, the inverter will report fault Err.15 and shutdown. 

34 

Frequency change 
enable 

If the function is set to be valid, when the frequency changes,the inverter 
does not respond to frequency changes until the terminal state is invalid. 

35 

PID action direction as 
reverse 

If the terminal is valid, PID action direction opposites to the direction 
set by E2.03 

36 

External parking 
terminal 1 

Under keyboard control mode, the terminal can be used to stop the 
inverter, same as STOP key on the keyboard. 

37 

Control command 
switch terminal 2 

Used to switch between terminal control and communication control. If 
the command source is selected as terminal control, the system will be 
switched to the communication control mode when the terminal is 
active; vice versa. 

38 

PID integral pause 

When the terminal is active, the PID integral adjustment function is paused, 
but the proportion and differential adjustments of PID are still valid. 

39 

Switch between 
frequency source master 
setting and preset 
frequency 

When the terminal  is active, the frequency source A  is replaced by the 
preset frequency (F0.01) 

40 

Switch between 
frequency source 
auxiliary setting and 
preset frequency 

When the terminal is active, the frequency source B is replaced with the 
preset frequency (F0.01) 

43 

PID parameter 
switching 

When DI terminal (E2.19 = 1) is used to switch PID parameters, if the 
terminal is invalid, PID parameters use E2.13 to E2.15; if the terminal 
is valid, PID parameters use E2.16 to E2.18 

44 

Custom fault 1 

When custom fault 1 and custom fault 2 are active, the inverter 
respectively alarms fault Err.27 and fault Err.28, and deals with them 
according to the mode selected by the fault protection action F8.19. 

45 

Custom fault 2 

48 

External parking 

In any control mode (Keyboard control, terminal control, communication 

Summary of Contents for PI500 011G2

Page 1: ...maintenance care For any problem within the warranty period please fill out the warranty card and fix it to our authorized dealer 2 Instructions on nameplate Model designation POWTRAN Inverter PI 500...

Page 2: ...ops LOCAL REMOTE Command indicator light That is the indicator for keyboard operation terminal operation and remote operation Communication contral ON terminal control working status OFF keyboard cont...

Page 3: ...range 0m to 6500m Running Input signal DI input terminal 6 digital input terminals DI5 for high speed pulse input 0 to 100 kHz square wave AI1 analog input 1 analog input terminals respectively for o...

Page 4: ...make sure that there is no mistake before power can be turned on 7 Parameter list In PI500A series frequency inverters some parameters are manufacturer reserved and their serial numbers are not liste...

Page 5: ...ting 0 Relative to maximum frequency 1 Relative to master frequency source 1 2 Relative to master frequency source 2 0 F0 06 Frequency source auxiliary setting range 0 to 150 100 F0 07 Frequency super...

Page 6: ...ed to switch between two frequency sources 19 UP DOWN setting Terminal keyboard When the frequency reference is the digital frequency this terminal is used to clear the changed frequency value by term...

Page 7: ...ad warning is exceeded For motor overload parameter setting refer to function codes F8 02 F8 04 7 Frequency inverter overload forecasting alarm The output signal ON 10 seconds before the overload prot...

Page 8: ...git SPA Ten thousands digit Relay 2 00000 F2 16 DA1 zero bias coefficient 100 0 to 100 0 0 0 F2 17 DA1 gain 10 00 to 10 00 1 00 F3 group Start stop control parameters group Code Parameter name Setting...

Page 9: ...verter module radiator temperature 0 0 to 100 0 F6 07 Total run time 0h to 65535h F6 08 Total power on time 0h to 65535h F6 09 Total power consumption 0 to 65535kWh F6 10 Product series number Frequen...

Page 10: ...0 to 300 0 Rated motor current 0 0 F7 40 Module temperature arrival 0 to 100 75 F7 41 Cooling fan control 0 Fan running only when running 1 Fan always running 0 F7 42 Timing function selection 0 Inval...

Page 11: ...depth 0 E0 group Pendulum frequency fixed length and counting parameter array Code Parameter name Setting range Factory setting Chan ge E0 00 Swing setting mode 0 Relative to center frequency 1 Relat...

Page 12: ...h 0 0s h E1 49 15 stage ac deceleration time selection Same as E1 19 0 E1 50 Simple PLC run time unit 0 S seconds 1 H hours 0 E1 51 Multi stage command 0 reference manner 0 Function code E1 00 referen...

Page 13: ...e Setting range Factory setting Cha nge y0 00 Parameter initialization 0 Nno operation 1 Restore default parameter values not including motor parameters 2 Clear history 3 Restore default parameter val...

Page 14: ...ppens 2 The control mode is vector and without identification of parameters 3 The deceleration time is too short 4 The voltage is low 5 Suddenly increase the load in the process of deceleration 6 Didn...

Page 15: ...2 Replace hall device 21 Err 21 Motor parameter auto tuning fault 1 The motor parameters was not set according to the nameplate 2 The identification process of parameter is timeout 1 correctly set mot...

Page 16: ...yboard compartment Dimension drawing of keyboard compartment dimension unit mm PI500 pI500A keyboard installation opening dimension drawing Mounting panel Opening size of external mounting panel Openi...

Reviews: