14--6
Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM
164201373 Rev. A
092402
14.5.2 Configuring the Modem to Call a Remote Computer
To configure the modem to call a remote computer, perform the following
procedure:
NOTE:
The brackets ([ ]) in the following steps indicate characters that require
keying in prior to pressing [ENTER].
1. Connect the modem to the PC through the serial port as described in the modem
manufacturer’s manual .
2. Key in [A], [T], then press [ENTER].
3. Confirm that the modem responds with “OK” or “0” (zero).
NOTE:
In steps 4 and 5, the “xxxxxxx” is the phone number of a remote computer.
The phone number should include all local line and long distance access
numbers needed to dial out. This number is limited to 32 characters. For
example, use “9” if needed for an outside line, “1” for long di (Area
Code) + Number or whatever access codes are needed to dial the call
directly. Add a “,” in the number anywhere that a delay is needed. This will
cause a one-second delay. More than one delay may be added to the
number; for example, enter “AT&Z0=T,9,,1 (Area Code) (Phone Number)”.
4. To program a group one number, key in [A], [T], [&], [Z], [0] (zero), [=], [T], [,],
[xxxxxxx], then press [ENTER].
5. To program a group two number, key in [A], [T], [&], [Z], [1], [=], [T], [,], [xxxxxxx],
then press [ENTER].
6. Confirm that the modem responds with “OK” or “0” (zero).
7. Key in [A], [T], [&], [W], [0] (zero), then press [ENTER].
9. Confirm that the modem responds with “OK” or “0” (zero).
8. Key in [A], [T], [&], [Y], [0] (zero), then press [ENTER].
9. Confirm that the modem responds with “OK” or “0” (zero).
10. Connect a telephone line to the modem and test the modem by keying in [A], [T],
[D], [S], = [0] (zero), then pressing [ENTER].
11. The modem dials the telephone number stored in step 4. (The number is
displayed on the terminal screen as it is dialed.) Repeat steps 4 through 9 as
necessary to modify the telephone number.
12. Confirm that the modem responds with “1” (one) or ”Connect” when the
connection is made.
NOTE:
To set up a group one or group two pager number, refer to “Configuring the
Modem to Call a Numeric Pager” section of this chapter.
Summary of Contents for 9315s