10--10
Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM
164201373 Rev. A
092402
10.3.3 Auto Start
NOTE:
Autorestart must be enabled to use this procedure.
1.
Perform the Initial Setup procedures.
2.
On SSBM, turn the
SYSTEM MODE
key switch to
BYPASS
momentarily.
3.
Observe that CBP and FBP have closed.
4.
On all UPMs, set
BATTERY
switch to
ENABLE
.
5.
On SSBM, turn the
SYSTEM MODE
key switch to
NORMAL
momentarily.
The UPS CB1 breakers close.
The rectifiers and input/rectifier cooling blowers turn on.
All CB2 (MBB) UPS battery breakers close.
NOTE:
If CB2 is a manual battery breaker, manually close CB2 after UPM
Battery Disconnected alarm and notification is received.
All inverter and output/inverter cooling blowers turn on. When the inverters reach full
voltage, the UPS CB3 breakers close. It takes less than one minute for the UPMs to
achieve Normal mode.
The UPMs are now ready to supply power to the critical load.
6.
Once the Parallel Capacity/Redundant system is redundant, the critical load is
automatically transferred from bypass to the UPMs via the CBS breaker and
system is operating in Normal mode.
NOTE:
If transfer is not completed within one minute, the
SYSTEM MODE
key
switch must be turned momentarily to
NORMAL
again to achieve normal
operation.
10.3.4 Single UPM Shutdown
NOTE:
If system is not redundant, UPM cannot be shut down using this procedure.
1.
On UPM, turn the
MODE
key switch to
BYPASS
for three seconds.
2.
Verify that UPS breakers CB1 and CB3 and battery breaker CB2 (MBB) are
open and the UPM powers down.
3.
On SSBM monitor screen, verify UPS OFF, message appears.
WARNING:
Power is present at UPM CB1 input, until
upstream UPM input feeder circuit
breaker is opened. The
load side of CB3 will still have voltage present.