10--14
Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM
164201373 Rev. A
092402
10.3.12 Resetting the Parallel Capacity/Redundant System after
EMERGENCY UPM OFF
CAUTION:
Do not attempt to restart the system after
Emergency UPM Off
until the cause
of the emergency has been identified and cleared.
The Emergency UPM Off
PUSH IN TO RESET
pushbutton is a small white button
on the SSBM Control/Monitor Panel. The
PUSH TO RESET
pushbutton pops out
when the Emergency UPM Off pushbutton on the SSBM Control/Monitor Panel is
activated.
To reset the Parallel Capacity/Redundant system:
1.
Press the Emergency UPM Off
PUSH IN TO RESET
pushbutton until it clicks
in and remains recessed.
2.
The Parallel Capacity/Redundant system is now reset. To restart the Parallel
Capacity/Redundant system, follow the procedure at the beginning of this
chapter.