A---44
Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM
164201373 Rev. A
092402
Table O. UPM Output-to-SSBM Cable and Conduit Configurations: Based on UPM Manuals
UPM Output-to-SSBM Cable Configuration
Minimum Conductor Size, 3
∅
, (1) Neutral, (1) Gnd
Max No. of UPMs Connectable to each SSBM
(Based on UPM-to-SSBM Cable Configuration
9315
Model - kVA/kW
Output
Voltage
Output
Current
Conductor Size
(AWG or kcmil)
Number of
Conductors per
∅
and Neutral
Number and
Size of Conduit
(in inches)
Model 2500
Model 3000
Model 4000
200 --- 200/160
400
290
4/0
2
2 --- 2.0
7
7
7
225 --- 225/180
208
625
350
3
3 --- 2.0
4
4
4
225 --- 225/180
480
271
3/0
2
1 --- 2.0
7
7
7
300 --- 225/180
480
271
3/0
2
1 --- 2.0
7
7
7
300 --- 225/180
600
217
350
1
1 --- 2.0
8
8
8
300 --- 300/240
208
830
500*
3
3 --- 3.0
4
4
4
300--- 300/240
480
360
250
2
2 --- 2.0
7
7
7
300--- 300/240
600
289
4/0
2
2 --- 2.0
7
7
7
250 --- 200/160
400
290
4/0
2
2 --- 2.0
7
7
7
250 --- 250/200
400
360
250
2
2 --- 2.0
7
7
7
400 --- 300/240
400
433
3/0
3
3 --- 2.5
4
4
4
400 --- 400/320
400
577
250
3
3 --- 2.5
4
4
4
500 --- 400/320
208
1110
600*
5
5 --- 3.0
2
2
2
500 --- 400/320
480
480
250
3
3 --- 3.0
4
4
4
500 --- 500/400
480
601
350
3
3 --- 3.0
4
4
4
500 --- 500/400
600
601
350
3
3 --- 3.0
4
4
4
625 --- 500/400
400
722
300
4
3 --- 3.0
3
3
3
625 --- 500/450
400
722
300
4
3 --- 3.0
3
3
3
625 --- 625/500
400
902
500
4
3 --- 3.5
3
3
3
625 --- 626/562
400
902
500
4
3 --- 3.5
3
3
3
750 --- 625/500
480
752
500
3
3 --- 3.0
4
4
4
750 --- 625/500
600
601
350
3
3 --- 3.0
4
4
4
750 --- 625/562
480
752
500
3
3 --- 3.0
4
4
4
750 --- 625/562
600
601
350
3
3 --- 3.0
4
4
4
750 --- 750/600
480
902
400
4
3 --- 3.5
3
3
3
750 --- 750/600
600
722
500
3
3 --- 3.0
4
4
4
750 --- 750/675
480
902
400
4
3 --- 3.5
3
3
3
750 --- 750/675
600
722
500
3
3 --- 3.0
4
4
4
DESCRIPTION:
DRAWING NO:
SHEET:
164201373---14
UPM OUTPUT-TO-SSBM CABLE AND
1 of 2
CONDUIT CONFIGURATIONS
NOTES:
1. * = Connections to output transformer, not UPM. Refer to applicable Powerware 9315 UPS Installation manual for UPS cable requirements
between the UPS and its output transformer.
Summary of Contents for 9315s