11--4
Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM
164201373 Rev. A
092402
11.5
Relay Interface Module
An optional Relay Interface Module (RIM) uses relay contact closures to indicate
the operating status and alarm condition of the Parallel Capacity/Redundant
system . A maximum of two monitoring accessories (RMPs, RIMs, or SCMs) can
be installed. See Table 11---1 for the number of accessories permitted. Figure
11---2 shows the RIM with its four 15-pin connectors labeled J1 through J4.
Figure 11---2. Relay Interface Module
The RIM can provide these signals:
•
UPS AVAILABLE
(pins 1 and 12) Contacts are closed when the UPS is
offline.
•
UPS OFF LINE
(pins 3 and 13) Contacts are closed when the UPS is
operating in Normal mode.
•
UTILITY FAILURE
(pins 6 and 15) Contacts are closed when Utility Failure is
detected.
•
BATTERY WEAK
(pins 5 and 14) Contacts are closed when approximately
2 minutes of battery time is remaining, before the critical
load is lost.