5--3
Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM
164201373 Rev. A
092402
4.
Connect RIM wiring to the terminal block using the terminations shown in
Table 5---1.
Table 5---1. RIM Wire Terminations
From RIM A
To SSBM
Remarks
TB1---4
TB3---1
TWISTED WIRES (4)
TB1---5
TB3---2
TWISTED WIRES (4)
1---2 TURNS PER
TB1---6
TB3---3
1 2 TURNS PER
3 INCHES
TB1---7
TB3---4
From RIM B (if used)
To SSBM
Remarks
TB1---4
TB3---5
TWISTED WIRES (4)
TB1---5
TB3---6
TWISTED WIRES (4)
1---2 TURNS PER
TB1---6
TB3---7
1 2 TURNS PER
3 INCHES
TB1---7
TB3---8
5.
Contact your local field service office for verification and testing of the RIM
and its connections prior to making connections to J1---J4.
You can order interface cables separately for connecting to the 15-Pin D-Sub
Connectors.
6.
Repeat steps 1 through 5 for each RIM you are installing.
7.
If you are installing an RMP or SCM in addition to an RIM, proceed to Chapter
4 or 6, respectively; otherwise, secure the SSBM by reversing the steps
contained in procedure “To Prepare the SSBM for Wiring to an RMP, RIM,
SCM, or Remote EPO” of Chapter 2.