4-12
4. Remove the small parts from the knockout in the right side plate.
5. Route and install RJ-45 Controller Area Network (CAN) cables between the UPS cabinets. See Figure 4-7,
Figure 4-11 and Figure 4-12 for wiring information.
6. Route and install pull chain wiring (Twisted Wires 0.5-2.0 mm
2
) between the UPS cabinets and cabinet
MOBs. See Figure 4-7, Figure 4-10 and Figure 4-11 for wiring information.
7.
If wiring Mini-Slot connections, proceed to paragraph 4.5.3;
4.5.3 Installing Mini-Slot Interface Connections
For installation and setup of an Mini-Slot card, contact an service representative (see paragraph 1.8)
To install wiring:
1.
If not already installed, install the LAN drop.
2. Route and install the LAN and other cables to the appropriate Mini-Slot cards. See Figure 4-6 and Figure 4-7
for Mini-Slot communication bay locations.
3. Refer to the manual supplied with the Mini-Slot card for operator instructions.
4. Install the power terminal cover using the provided hardware.
LAN drop for connection to UPS communications card is to be supplied by
customer.
NOTE