3-20
There is no DC disconnect device within the UPS. A battery disconnect switch is recommended, And may be
required by local codes when batteries are remotely located. The battery disconnect switch should be installed
between the battery and the UPS
External DC input overcurrent protection and disconnect switch for the remote battery location is to be
provided by the user. Table 3-9 lists the maximum rating for continuous-duty rated circuit breakers satisfying the
criteria for both.
Battery voltage is computed at 2 volts per cell. Rated battery current is computed at 2 volts per cell. The battery
wiring used between the battery and the UPS should not allow a voltage drop of more than 1% of nominal DC
voltage at rated battery current. If the conductors used for DC input from the battery cabinets to the UPS are
those provided by the UPS manufacturer, and the UPS and battery cabinets are manufactured by the same
supplier, then it is acceptable if they do not meet the noted minimum conductor sizes.
Table 3-9. Recommended DC input circuit breaker rating
Circuit Breaker Rating
UPS Model
Load Derating
Rated battery voltage (DC 432V)
Rated battery voltage(DC 384V)
80% Derated
57A
64A
100% Rating
46A
52A
80% Derated
86A
97A
100% Rating
69A
77A
80% Derated
114A
129A
100% Rating
92A
103A
80% Derated
172A
193A
100% Rating
137A
155A
80% Derated
229A
258A
100% Rating
183A
206A
VFI 20000TAP
VFI 30000TAP
VFI 40000TAP
VFI 60000TAP
VFI 80000TAP
Summary of Contents for VFI 20000-40000TAP 3/3 BI
Page 2: ......
Page 4: ......
Page 8: ...iv This page intentionally left blank...
Page 10: ...vi This page intentionally left blank...
Page 12: ...viii This page intentionally left blank...
Page 18: ...1 6 This page intentionally left blank...
Page 21: ...Section 1 Installation...
Page 22: ......
Page 46: ...This page intentionally left blank 3 24...
Page 64: ...4 18 Notes...
Page 65: ...Section 2 Operation...
Page 66: ......