08: Bypass frequency range setting
Interface
Configuração
Parameter 2 & 3:
Set the acceptable high frequency
point and acceptable low frequency point for Bypass mode
by pressing the Down key or Up key.
HLS:
Bypass high frequency point
For 50Hz output frequency models:
51-55Hz:
setting the frequency high loss point from 51Hz
to 55HZ(Default: 53.0Hz)
For 60Hz output frequency models:
61-65Hz:
setting the frequency high loss point from 61Hz
to 65Hz(Default: 63.0Hz)
LLS:
Bypass low Frequency point
For 50Hz output frequency models:
45-49Hz:
setting the frequency low loss point from 45Hz
to 49HZ(Default: 47.0Hz)
For 60Hz output frequency models:
55-59Hz:
setting the frequency low loss point from 55Hz
to 59Hz(Default: 57.0Hz)
09: Saídas programáveis ativadas / desativadas
Interface
Configuração
Parâmetro 3:
Saídas programáveis ativadas ou
desativadas
ENA: Saídas programáveis ativadas
DIS: Saídas programáveis desativadas (Standard)
10: Configuração das saídas programáveis
Interface
Configuração
Parâmetro 3:
Fixa os limites do tempo de autonomia das
tomada programáveis.
0-999: ajusta o tempo de autonomia (durante o modo
bateria) de 0 a 999 minutos para as saídas programáveis
conectadas aos dispositivos não-críticos.
11: Configuração das saídas gerais
Interface
Configuração
Parâmetro 3:
Fixa os limites do tempo de autonomia das
tomadas para as cargas críticas.
0-999:
ajusta o tempo de autonomia de 0 a 999 minutos
para as saídas gerais em modo bateria.
0:
Quando o valor é "0", o tempo de autonomia é de
apenas 10 segundos.
DIS:
Disable the autonomy limitation and the backup time
will depend on battery capacity. (Standard)