19
EN
6. Specifications
MODEL
1000
1500
2000
3000
CAPACITY*
1000 VA / 900 W 1500 VA / 1350 W 2000 VA / 1800 W 3000 VA / 2700 W
INPUT
Voltage
Range
Low Line Transfer
160 VAC / 140 VAC / 120 VAC / 110 VAC ± 5 % or 80 VAC / 70 VAC / 60 VAC / 50 VAC ± 5 %
( based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
Low Line Comeback
175VAC/155VAC/135VAC/125VAC ± 5 % or 87VAC/77VAC/67VAC/62VAC ± 5 %
High Line Transfer
300 VAC ± 5 % or 150 VAC ± 5 %
High Line Comeback
290 VAC ± 5 % or 145 VAC ± 5 %
Frequency Range
40Hz ~ 70 Hz
Phase
Single phase with ground
Power Factor
≧
0.99 @ 220-230 VAC or 110-120 VAC
OUTPUT
Output voltage
200/208/220/230/240VAC or 100/110/115/120/127 VAC
AC Voltage Regulation
± 1% (Batt. Mode)
Frequency Range
(Synchronized Range)
47 ~ 53 Hz or 57 ~ 63 Hz
Frequency Range (Batt. Mode)
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
Current Crest Ratio
3:1
Harmonic Distortion
≦
2 % THD (Linear Load)
≦
4 % THD (Non-linear Load)
Transfer
Time
AC Mode to Batt. Mode
Zero
Inverter to Bypass
4 ms (Typical)
Waveform (Batt. Mode)
Pure Sinewave
EFFICIENCY
AC Mode
90%
90%
Battery Mode
86%
86%
88%
89%
BATTERY
Standard
Model
Battery Type
12 V / 7 AH
12 V / 9 AH
12 V / 7 AH
12 V / 9 AH
Numbers
3
3
6
6
Recharge Time
4 hours recover to 90% capacity (Typical)
Charging Current
1.5 A(max.)
Charging Voltage
41.0 VDC ± 1%
82.1 VDC ±1%
Long-run
Model
Battery Type &
Numbers
Depending on the capacity of external batteries
Charging Current
1.0 A/2.0 A/4.0A/6.0 A /8.0 A(max.) (Selectable via LCD setting)
Charging Voltage
41.0 VDC ± 1%
82.1 VDC ±1%
PHYSICAL
Tower
Case
Dimension, D X W X H
397 X 145 X 220 (mm)
421 X 190 X 318 (mm)
Net Weight (kgs)
12.5
5.8
13.8
5.8
25.8
12
27
13.2
Rack
Case
Dimension, D X W X H
420x438x88[2U] (mm)
580x438x133[3U] (mm)
Net Weight (kgs)
16
10
17
10
29
17
31
17
ENVIRONMENT
Operation Humidity
20-95 % RH @ 0- 40°C (non-condensing)
Noise Level
Less than 45dBA @ 1 Meter
MANAGEMENT
Smart RS-232 or USB
Supports Windows®2000/2003/XP/Vista/2008/7/8, Linux, Unix and MAC
Optional SNMP
Power management from SNMP manager and web browser
* Derate capacity to 80% of capacity in Frequency converter mode and to 80% when the output voltage is adjusted to 100VAC,
200VAC or 208VAC.