12
FR
08: Bypass frequency range setting
Interface
Valeur
Parameter 2 & 3:
Set the acceptable high frequency point
and acceptable low frequency point for Bypass mode by
pressing the Down key or Up key.
HLS:
Bypass high frequency point
For 50Hz output frequency models:
51-55Hz:
setting the frequency high loss point from 51Hz to
55HZ(Default: 53.0Hz)
For 60Hz output frequency models:
61-65Hz:
setting the frequency high loss point from 61Hz to
65Hz(Default: 63.0Hz)
LLS:
Bypass low Frequency point
For 50Hz output frequency models:
45-49Hz:
setting the frequency low loss point from 45Hz to
49HZ(Default: 47.0Hz)
For 60Hz output frequency models:
55-59Hz:
setting the frequency low loss point from 55Hz to
59Hz(Default: 57.0Hz)
09: Activation/désactivation des sorties programmables
Interface
Valeur
ENA : active les sorties programmables
DIS : désactive les sorties programmables (Standard)
10: Configuration des sorties programmables
Interface
Valeur
0-
999 : réglage de l’autonomie en minutes de 0 à 999 pour
les prises sorties programmables connectées aux charges
non-prioritaires en mode Batteries.
(
Default
: 999)
11: Configuration des prises générales.
Interface
Valeur
Paramètre 3:
Réglage de l’autonomie des prises générales
en mode batterie.
0-999:
Réglage du temps d’autonomie en minutes de 0
-999
pour les sorties génerales en mode batterie.
DIS:
Disable the autonomy limitation and the backup time
will depend on battery capacity. (Standard)
0:
Quand la valeur est “0”, le temps d’autonomie est de 10
secondes.