12
P1
: work mode setting:
01: Mains priority mode
02: Energy saving mode
03: Battery priority mode
04:Unnatended mode
05: Solar mode (option Internal
MPPT Charger)
P2
: Battery type and charging voltage setting:
SLD: sealed lead-acid battery, FLD: flooded lead
battery, GEL: gel battery, LI: lithium battery, USE:
user mode (default). If user mode is selected, adjust
battery voltage in P3 and P4 menus. If you do not
select the USE (user mode), the P3 and P4 menus
will not show.
P4
: Battery voltage floating charge setting:
12.9
~
13.8 (single) can be set
P3
: Battery voltage uniform charge setting:
Max voltage when charging before going to
Float
13.6V
~
15.5V (single)