Cyberhawk-200M Installation
-
2 of 22 -
Doc. No: 202-003318-610 Rev A01
RECEIVING
The
Cyberhawk-200M-xP
Multi Power Meter is packaged for shipping in a reinforced cardboard box
together with mounting hardware and manuals. CTs and Interface terminals may also be included in
the shipment packaged in separate boxes. Unpack and inspect equipment for damage that might
have occurred during shipment. Also check the packing list to ensure all the equipment is accounted
for (note accessories may be shipped in separate packages).
Claims for damages should be made to the carrier immediately and also notify Powersmiths
International of the details. Claims for shortages should be made to Powersmiths International at the
earliest opportunity.
HANDLING
The units may weigh up to 50 lbs (~ 22kg) which may require two persons to handle it comfortably.
Handle the unit in such a way to protect the Displays and avoid rough surfaces that may mar or
scratch the surface of the case.
STORAGE
No special precautions need be taken in storing this device other that it should be protected from
moisture or excessive humidity. Storage temperatures should not exceed the limits of – 25 °C to + 60
°C
INSTALLATION GUIDELINES
This equipment is to be installed in accordance with the prevailing local and National Electric
Codes such as National Electric Code (NEC) in the USA or Canadian Electric Code in Canada,
which governs the requirements for electrical wiring and protection. These requirements will
include, but not limited to:
Note: This device is not intended as a utility meter or for use ahead of branch-circuit protection
Branch circuit protection devices for connection to the voltage bus(es) (not supplied)
Use of an appropriate and approved Current Transformers (CTs) for installation on the
current carrying buses (available from Powersmiths on separate order only)
Separation of Primary (Voltage Input) and Secondary wiring (CT and Digital Inputs,
Communication)
The following points should be considered in choosing a location:
Environmental rating (Type 1 is for dry protected environments)
Accessibility including clearance for the door swing
Location relative to associated Disconnects and CTs
Viewing height for displays
NOTICE
SAFETY INSTRUCTIONS
Read and follow these instructions
Use appropriate personal protective equipment and follow safe electrical work
practices (eg. NPA 70E)
This equipment to be installed and serviced only by qualified competent
electrical personnel that have appropriate training on Electrical Systems
This device is to be installed in accordance with the prevailing local and
National Electric Codes
Failure to observe and follow these installation instructions and
procedures could result in serious injury or even death
!