Troubleshooting
5.1
ALARM CODES AND ERROR MESSAGES
The AURORA MICRO Inverter is capable of
communicating errors/warnings via radio to the
associated CDD device. Any messages received
and related codes can be checked on the display
of the CDD device
Table 5-1 below provides a description of the
alarm messages and error codes.
Table 5-1: Alarm Messages and Error Codes
Alarm
Messages
Code
displayed
Cause
Solution
Input OC
E001
The error appears when the inverter input
current exceeds the set overcurrent
threshold. This may be caused by:
a) sudden irradiance changes that may
generate input current surges into the
MICRO inverter
b) PV module incompatible with the
MICRO-inverter input characteristics
c) Faulty MICRO-inverter
a) The error occurs sporadically and no
action is required as the MICRO-inverter will
automatically reset to normal operation
b) It is necessary to verify that the
photovoltaic module specifications are
compatible with the inverter.
c) If conditions a) and b) have been verified
and the error persists, the malfunction may
be caused by an internal inverter fault
Vbulk OV
E004
The error is generated when the voltage at
the ends of the bulk capacitors exceeds the
Over Voltage threshold. This may be
caused by:
a) Grid voltage too high
b) Internal inverter fault
a) Check that the grid voltage is compatible
with the MICRO-inverter specifications. In
the event of highly abnormal grid voltage,
please contact your grid operator to address
the problem.
b) If no problems are found when checking
the grid voltage, the alarm may be caused
by internal inverter faults.
Output OC E006
The error appears when the inverter output
current exceeds the internal inverter alarm
threshold.
This may be caused by:
a) High impedance grid with significant
voltage variations, even with small loads.
b) Internal inverter fault
a) Check that the grid voltage is stable,
mainly upon:
- loading with high current peak loads.
- maximum power generation of the PV
system
If the grid voltage is unstable, verify the
appropriate sizing of the line cable/s, and, if
correct, please contact your grid operator to
address the problem.
b) If no problems are found when checking
the grid voltage, the alarm may be caused
by internal inverter faults
Summary of Contents for Aurora CCD
Page 1: ...THE MANUAL AURORA CDD...
Page 5: ...Page 4 of 80 Instruction Manual for AURORA CDD BCG 00613_AA PART 1 INTRODUCTION AND SAFETY...
Page 18: ...Page 17 of 80 Instruction Manual for AURORA CDD BCG 00613_AA PART 3 MOUNTING AND CONFIGURATION...
Page 34: ...Page 33 of 80 Instruction Manual for AURORA CDD BCG 00613_AA PART 4 OPERATIONS GUIDE...
Page 69: ...Page 68 of 80 Instruction Manual for AURORA CDD BCG 00613_AA PART 5 TROUBLESHOOTING...
Page 74: ...Page 73 of 80 Instruction Manual for AURORA CDD BCG 00613_AA PART 6 MAINTENANCE GUIDE...
Page 78: ...Page 77 of 80 Instruction Manual for AURORA CDD BCG 00613_AA PART 7 APPENDIX...