Parameter
Name / Description
Value
G4: Inputs – S4.1: Digital Inputs.
5 DIGITL IN 1=50
G4.1.5
/ Multi-function Digital Input 1
configuration
50
PMP START/STP (Automatic starting of the system).
6 DIGITL IN 2=63
G4.1.6
/ Multi-function Digital Input 2
configuration
63
SETPONT PIN1 (low bit configuration for the selection of
multiple setpoints).
7 DIGITL IN 3=64
G4.1.7
/ Multi-function Digital Input 3
configuration
64
SETPONT PIN2 (middle bit configuration for the selection of
multiple setpoints).
8 DIGITL IN 4=65
G4.1.8
/ Multi-function Digital Input 4
configuration
65
SETPONT PIN3 (high bit configuration for the selection of
multiple setpoints).
G4: Inputs – S4.3: Analogue Input 2.
1 SENSOR 2 ?=S
G4.3.1
/ To enable sensor of Analogue
Input 2
Y=YES
Ii allows enabling the sensor of the analogue input 2
that will be used for PID feedback.
2 SENSOR 2=Bar
G4.3.2
/ Selection of sensor 2 units
Bar
These units must be set according to type of sensor that
user will use in the installation.
3 AIN2 FORMAT=mA
G4.3.3
/ Analogue Input 2 Format
mA
These units must be set according to the type of sensor that
user will use in the installation.
4 4mA
G4.3.4
/ Minimum range of Analogue Input
2
+4mA
These units must be set according to the type of sensor
that user will use in the installation.
5 Smi2=+0.0Bar
G4.3.5
/ Minimum range of sensor 2
+0.0Bar
This range must be set according to the type of sensor
that user will use in the installation.
620mA
G4.3.6
/ Maximum range of Analogue Input
2
+20mA
These units must be set according to the type of sensor
that user will use in the installation.
7 Sma2=+10.0Bar
G4.3.7
/ Maximum range of sensor 2
+10.0Bar
This range must be set according to the type of
sensor that user will use in the installation.
G25: Pump Control – S25.1: Setpoints.
1 CONTROL MODE=1
G25.1.1
/ Control mode
1
Pumps. The drive will start in pump control mode.
5 SETPT1=1.0Bar
G25.1.5
/ Local setpoint 1 for the PID
1.0Bar
It allows user to set the value of the speed reference 1
for the equipment. (Set according to the requirements of the applic.)
6 SETPT2=2.0Bar
G25.1.6
/ Local setpoint 2 for the PID
2.0Bar
It allows user to set the value of the speed reference 2
for the equipment. (Set according to the requirements of the applic.)
7 SETPT3=3.0Bar
G25.1.7
/ Local setpoint 3 for the PID
3.0Bar
It allows user to set the value of the speed reference 3
for the equipment. (Set according to the requirements of the applic.)
8 SETPT4=4.0Bar
G25.1.8
/ Local setpoint 4 for the PID
4.0Bar
It allows user to set the value of the speed reference 4
for the equipment. (Set according to the requirements of the applic.)
9 SETPT5=5.0Bar
G25.1.9
/ Local setpoint 5 for the PID
5.0Bar
It allows user to set the value of the speed reference 5
for the equipment. (Set according to the requirements of the applic.)
10 SETPT6=6.0Bar
G25.1.10
/ Local setpoint 6 for the PID
6.0Bar
It allows user to set the value of the speed reference 6
for the equipment. (Set according to the requirements of the applic.)
11 SETPT7=7.0Bar
G25.1.11
/ Local setpoint 7 for the PID
7.0Bar
It allows user to set the value of the speed reference 7
for the equipment. (Set according to the requirements of the applic.)
12 SETPT8=8.0Bar
G25.1.12
/ Local setpoint 8 for the PID
8.0Bar
It allows user to set the value of the speed reference 8
for the equipment. (Set according to the requirements of the applic.)
G25: Pump Control – S25.2: PID Setting.
3 PID FBK=AI2
G25.2.3
/ PID feedback source
AI2
It allows selecting Analogue Input 2 as feedback signal for
PID regulator.
G25: Pump Control – S25.3: Start Conditions.
1 LP Pon=0.0Bar
G25.3.1
/ Wake up level of the drive
x.xBar
When demand decreases, the drive can go in sleep
mode. (It allows setting the wake up level for the drive. This value is
set as units of PID setpoint).
G25: Pump Control – S25.4: Stop Conditions.
1 LP T SLP=20s
G25.4.1
/ Delay time before activating sleep
mode
20s
This delay time will be applied to any conditions that
activate the sleep mode. These conditions are: sleep speed, No
Flow input, Flow measurement and sleep current. If anyone of them
is met, the time to activate sleep mode will start elapsing.
2 40.0%
G25.4.2
/ Sleep speed for local setpoint 1
+40.0%
It allows setting the sleep speed 1 below which the
drive will sleep whenever local setpoint 1 is selected. (Set
according to the installation).
3 42.0%
G25.4.3
/ Sleep speed for local setpoint 2
+42.0%
It allows setting the sleep speed 2 below which the
drive will sleep whenever local setpoint 2 is selected. (Set
according to the installation).
4 44.0%
G25.4.4
/ Sleep speed for local setpoint 3
+44.0%
It allows setting the sleep speed 3 below which the
drive will sleep whenever local setpoint 3 is selected. (Set
according to the installation).
5 46.0%
G25.4.5
/ Sleep speed for local setpoint 4
+46.0%
It allows setting the sleep speed 4 below which the
drive will sleep whenever local setpoint 4 is selected. (Set
according to the installation).
6 SLPsp=+48.0%
G25.4.6
/ Sleep speed for local setpoint 5
+48.0%
It allows setting the sleep speed 5 below which the
drive will sleep whenever local setpoint 5 is selected. (Set
according to the installation).
Summary of Contents for SD700 Series
Page 1: ...Variable Speed Drive Application Manual PUMPS...
Page 2: ......
Page 3: ...Variable Speed Drive Application Manual PUMPS Edition March 2011 SD70MTAP01BI Rev B...
Page 4: ...SD700 POWER ELECTRONICS 2...
Page 8: ...SD700 POWER ELECTRONICS 6 INDEX...
Page 61: ......
Page 63: ...www power electronics com...