FAULT MESSAGES. DESCRIPTIONS AND ACTIONS
Parameter Screen
Description
Address
Range
Modbus Range
G25.6.17
17 NO FLsp=+0.0%
Minimum stop speed because of No Flow
detection
42349
+0.0 to +250%
0 to 20480
G25.6.18
18 NO FLbyp=0.0s
Bypass time for No Flow switch
42350
0.0 to 999s
0 to 9990
G25.6.19
19 NO FLdly=0.0s
Trip delay time because of No Flow
42351
0.0 to 999s
0 to 9990
G25.6.20
20 CYCLE TI=0m
Cycle time of the drive
42353
OFF=0 to 99m
0 to 99
G25.6.21
21 CYCLE CNT=5
Cycle counter
42354
1 to 5
1 to 5
G25.7.1
1 PRESSU SOU=PID
Pressure reading source
42357
PID
AI1
AI2
0 to 2
G25.7.2
2 FILL SP=+70.0%
Speed for pipe filling process
42116
OFF=0.0; +0.1 to
+250%
0 to 20480
G25.7.3
3 FILL P=2.0Bar
Pressure for the end of pipe filling process
42117
0.0 to 3276
Engineering Units
0 to 32760
G25.7.4
4 FILL TIM=15m
Safety time for pipe filling process
42118
OFF=0; 1 to 9999min
0 to 9999
G25.7.5
5 SPT RAMP=1.0Bar / s
Setpoint ramp
42119
0.01 to 320.00
Engineering Units/s
0 to 32000
G25.8.1
1 COMP 1=0.0Bar
Compensation pressure at the starting of 1
fixed pump
42131
0.0 to 3276
Engineering Units
0 to 32760
G25.8.2
2 COMP 2=0.0Bar
Compensation pressure at the starting of 2
fixed pumps
42132
0.0 to 3276
Engineering Units
0 to 32760
G25.8.3
3 COMP 3=0.0Bar
Compensation pressure at the starting of 3
fixed pumps
42133
0.0 to 3276
Engineering Units
0 to 32760
G25.8.4
4 COMP 4=0.0Bar
Compensation pressure at the starting of 4
fixed pumps
42134
0.0 to 3276
Engineering Units
0 to 32760
G25.8.5
5 COMP 5=0.0Bar
Compensation pressure at the starting of 5
fixed pumps
42135
0.0 to 3276
Engineering Units
0 to 32760
G25.9.1
1 ENABLE PUMP1=N
To enable fixed pump associated to output
relay 1
42136
N
Y
0 to 1
G25.9.2
2 ENABLE PUMP2=N
To enable fixed pump associated to output
relay 2
42137
N
Y
0 to 1
G25.9.3
3 ENABLE PUMP3 =N
To enable fixed pump associated to output
relay 3
42138
N
Y
0 to 1
G25.9.4
4 ENABLE PUMP4=N
To enable fixed pump associated to analogue
output 1
42148
N
Y
0 to 1
G25.9.5
5 ENABLE PUMP5=N
To enable fixed pump associated to analogue
output 2
42149
N
Y
0 to 1
G25.9.6
6 FP ALTER MOD=0
Alternation mode of fixed pumps
42139
0 to 2
0 to 2
G25.9.7
7 JPon P=0.0Bar
Starting pressure of Jockey pump
42371
0.0 to 3276
Engineering Units
0 to 32760
G25.9.8
8 JPon DLY=20s
Start delay time for Jockey pump
42372
0 to 600s
0 to 6000
G25.9.9
9 JPof P=0.0Bar
Stopping pressure of Jockey pump
42373
0.0 to 3276
Engineering Units
0 to 32760
G25.9.10
10 PRp BYP=300s
Bypass time for Priming pump
42102
0.1 to 6000s
0 to 60000
G25.9.11
11 PRp DLY=OFF
Trip time of F72 during Priming pump is
connected
42103
OFF=0; 0.1 to 6000m
0 to 60000
G25.9.12
12 SUPPLY PUMP=0
Selection of Auxiliary Pump as Priming or Lift
Pump
42418
0 to 1
0 to 1
G25.10.1
1 FLOW SEL=PULSE
Flow reading source
42141
AI1
AI2
PULSE
0 to 2
G25.10.2
2 MAX FLOW=1000 l/s
Maximum allowed flow
42143
0.0 to 3276
Engineering Units
0 to 32760
G25.10.3
3 0%
Offset percentage over maximum flow
42144
+0% to +250%
0 to 20480
G25.10.4
4 FLO RES=+100%
Flow percentage to reset algorithm
42145
+0.0 to +100%
0 to 100
G25.10.5
5 2.0% / s
Deceleration ramp during algorithm
42146
+0.0 to +250% /s
0 to 20480
G25.10.6
6 UNIT FLOW= l/s
Units of measurement of instantaneous flow
42147
-
0 to 9
G25.11.1
1 P1 = -----0d -----0m
Operated time by Pump 1
42011 – m
42014 – d
-
Real value = Modbus value
G25.11.2
2 P2 = -----0d -----0m
Operated time by Pump 2
42012 – m
42015 – d
-
Real value = Modbus value
G25.11.3
3 P3 = -----0d -----0m
Operated time by Pump 3
42013 – m
42016 – d
-
Real value = Modbus value
G25.11.4
4 P4 = -----0d -----0m
Operated time by Pump 4
42018 – m
42020 – d
-
Real value = Modbus value
G25.11.5
5 P5 = -----0d -----0m
Operated time by Pump 5
42019 – m
42021 – d
-
Real value = Modbus value
G25.11.9
TIME RESTORE=N
Reset counters
42017
N
Y
0 to 1
Summary of Contents for SD700 Series
Page 1: ...Variable Speed Drive Application Manual PUMPS...
Page 2: ......
Page 3: ...Variable Speed Drive Application Manual PUMPS Edition March 2011 SD70MTAP01BI Rev B...
Page 4: ...SD700 POWER ELECTRONICS 2...
Page 8: ...SD700 POWER ELECTRONICS 6 INDEX...
Page 61: ......
Page 63: ...www power electronics com...