POWER ELECTRONICS
SD700
DESCRIPTION OF PROGRAMMING PARAMETERS
15
3.
The different parameters of the SD700 are displayed in the alphanumeric LCD. These parameters are
organized in groups (G1
, G2, G3, …).
The most of parameters related to the pump control are included in Group 25, except for the settings of the
in puts and outputs, that are included in groups G4 and G8. Also, there are some visualizing parameters
included in visualization groups SV.5 and SV.8 described before.
Therefore, all the parameters that affect to the pump macro are listed below.
3.1.
Group 1 – G1: Options Menu
Parameter
Name /
Description
Range
Function
Set on
RUN
7 PROG= STANDARD
G1.7
/ Program
activation
STANDARD
PUMP
It allows selection additional functionalities. If PUMP is selected, then
extended functionality for pumping control G25 will appear as available.
The group G25 will be hidden if the pump program is not active.
Once selected the pump program, a character will appear in the upper
line of the display, beside the drive status, indicating constantly that the
pump program is active. The letter “b” in Spanish and the letter “p” for
English / German.
The most of parameters relative to the pump control are located in Group
25, excepting those setting relatives to inputs and outputs that can be
found in groups G4 and G7.
Additionally there are some visualization screens included in visualization
groups SV.5 and SV.8.
For additional information, see the „Pump Application Manual‟ for the
SD700.
YES
3.1.1.
Subgroup 1.10 – S1.10: Eloader (EEPROM Charger)
Parameter /
Default Value
Name /
Description
Range
Function
Set on
RUN
UPLOAD=N
G1.10.1
/ Saves
the parameters
of the drive to the
display.
N
Y
When adjusting this value to Yes, the copy of parameters to the display starts,
saving the configuration of the drive.
A screen will appear showing the uploading progress:
UPLOADING…100%
When this process is over, the progress screen will automatically return to the
main screen, set by default to No.
Note:
In order to carry out the parameter load correctly, the user should firstly
configure the digital inputs corncerning „STOP‟ functions before any other
function.
NO
DOWNLOAD=N
G1.10.2
/ Saves
the parameters
of the display to
the drive.
N
Y
When adjusting this value to Yes, the copy of parameters stored in the display to
the drive will start modifying and programming the parameters of this new drive.
A screen will appear showing the downloading progress:
DOWNLOADING …100%
When this process is over, the progress screen will automatically change to the
main screen, set by default to No.
Note:
Before downloading, read carefully the note refered to the digital inputs
configuration in Subgroup [4.1].
NO
Summary of Contents for SD700 Series
Page 1: ...Variable Speed Drive Application Manual PUMPS...
Page 2: ......
Page 3: ...Variable Speed Drive Application Manual PUMPS Edition March 2011 SD70MTAP01BI Rev B...
Page 4: ...SD700 POWER ELECTRONICS 2...
Page 8: ...SD700 POWER ELECTRONICS 6 INDEX...
Page 61: ......
Page 63: ...www power electronics com...