FAULT MESSAGES. DESCRIPTIONS AND ACTIONS
Parameter Screen
Description
Address
Range
Modbus Range
G25.1.1
1 CONTROL MODE=1
Control mode
42035
0 to 1
0 to 1
G25.1.2
2 MAN SPD REF= LOCAL
Source selection for speed reference in
manual mode
42041
LOCAL
AI1
AI2
0 to 2
G25.1.3
3 MAN SPEED=+0.0%
Value of speed reference for LOCAL source
in manual mode
42042
-250% to +250%
-20480 to +20480
G25.1.4
4 ALT MAN S R=LOCAL
Source for the Alternative speed reference in
manual mode
42043
LOCAL
AI1
AI2
0 to 2
G25.1.5
5 SETPT1=0.0Bar
Local setpoint 1 for PID
42151
0 to 3276
Engineering Units
0 to 32760
G25.1.6
6 SETPT2=0.0Bar
Local setpoint 2 for PID
42152
0 to 3276
Engineering Units
0 to 32760
G25.1.7
7 SETPT3=0.0Bar
Local setpoint 3 for PID
42153
0 to 3276
Engineering Units
0 to 32760
G25.1.8
8 SETPT4=0.0Bar
Local setpoint 4 for PID
42154
0 to 3276
Engineering Units
0 to 32760
G25.1.9
9 SETPT5=0.0Bar
Local setpoint 5 for PID
42155
0 to 3276
Engineering Units
0 to 32760
G25.1.10
10 SETPT6=0.0Bar
Local setpoint 6 for PID
42156
0 to 3276
Engineering Units
0 to 32760
G25.1.11
11 SETPT7=0.0Bar
Local setpoint 7 for PID
42157
0 to 3276
Engineering Units
0 to 32760
G25.1.12
12 SETPT8=0.0Bar
Local setpoint 8 for PID
42158
0 to 3276
Engineering Units
0 to 32760
G25.1.13
13 T AutOFF=OFF
Time for automatic stop
42044
OFF; 0.1 to 99.9h
0 to 9999
G25.2.1
1 PID SETP=LOCAL
PID setpoint source
42045
LOCAL
AI1
AI2
0 to 2
G25.2.2
2 PID aSTP=LOCAL
Alternative PID setpoint source
42374
LOCAL
AI1
AI2
0 to 2
G25.2.3
3 PID FBK=AI2
PID feedback source
42046
AI1
AI2
PULSE
0 to 2
G25.2.4
4 PID Kc=1.0
Proportional gain of PID regulator
42047
0.1 to 20
1 to 200
G25.2.5
5 PID It=5.0s
Integral time of PID regulator
42048
0.1 to 999.9s, Max.
1 to 9999; 10000
G25.2.6
6 PID Dt=0.0s
Derivation time of PID regulator
42049
0.0 to 250s
0 to 2500
G25.2.7
7 PID ERR=+xx.x%
Error of PID regulator
42050
+0 to +100%
--32768 to 32768
G25.2.8
8 ERR=+xx.xxkPa
Error of PID regulator in engineering units
42051
+0.0 to +3276
Engineering Units
---32768 to 32768
G25.2.9
9 PID INVERT=N
PID output inversion
42326
N
Y
0 to 1
G25.3.1
1 LP Pon=0.0%
Wake up level of the drive
42064
0.0 to 3276Bar
0 to 32760
G25.3.2
2 FP SpON=+90.0%
Start speed for the fixed pumps
42055
-250% to +250%
-20480 to +20480
G25.3.3
3 FP ErON=+10.0%
Minimum PID error to start the fixed pumps
42056
OFF=0 to +200%
0 to 16384
G25.3.4
4 FP T1 ON=10s
Delay time to start fixed pump 1 (Relay 1)
42062
OFF=0 to 6000s
0 to 60000
G25.3.5
5 FP T2 ON=10s
Delay time to start fixed pump 2 (Relay 2)
42065
OFF=0 to 6000s
0 to 60000
G25.3.6
6 FP T3 ON=10s
Delay time to start fixed pump 3 (Relay 3)
42066
OFF=0 to 6000s
0 to 60000
G25.3.7
7 FP T4 ON=10s
Delay time to start fixed pump 4 (AO1)
42067
OFF=0 to 6000s
0 to 60000
G25.3.8
8 FP T5 ON=10s
Delay time to start fixed pump 5 (AO2)
42068
OFF=0 to 6000s
0 to 60000
G25.4.1
1 LP T SLP=20s
Delay Time before activating sleep mode
42306
OFF=0; 1 to 999s
0 to 9990
G25.4.2
2 40.0%
Sleep speed for local setpoint 1
42307
+0.0 to +250%
0 to 20480
G25.4.3
3 40.0%
Sleep speed for local setpoint 2
42308
+0.0 to +250%
0 to 20480
G25.4.4
4 40.0%
Sleep speed for local setpoint 3
42309
+0.0 to +250%
0 to 20480
G25.4.5
5 40.0%
Sleep speed for local setpoint 4
42310
+0.0 to +250%
0 to 20480
G25.4.6
6 40.0%
Sleep speed for local setpoint 5
42311
+0.0 to +250%
0 to 20480
Summary of Contents for SD700 Series
Page 1: ...Variable Speed Drive Application Manual PUMPS...
Page 2: ......
Page 3: ...Variable Speed Drive Application Manual PUMPS Edition March 2011 SD70MTAP01BI Rev B...
Page 4: ...SD700 POWER ELECTRONICS 2...
Page 8: ...SD700 POWER ELECTRONICS 6 INDEX...
Page 61: ......
Page 63: ...www power electronics com...