PowlVac® ASD 27kV & 38kV Vacuum Circuit Breaker
IB-65100
Installation
Figure 14
Push to Trip Knob & Racking Access
Door
a
b
a. Push to Trip Knob
b. Racking Access Door
Note:
The compartment door is removed for
clarity.
h. Close and latch the compartment door.
i. Insert racking handle (Figure 15, b)
into the racking access door and rack
the circuit breaker in. Once the circuit
breaker is fully connected, the racking
indicator flag (Figure 15, a) will display
CONNECTED.
Figure 15
Racking Indicator Flags & Racking
Handle
a
b
a. Racking Indicator Flag
b. Racking
Handle
Note:
The compartment door is removed for
clarity.
j. Remove the racking handle and close the
racking access door.
Once you have completed steps a through j,