Publication No. 5106227
7
Flue Air
Flue Air
2˚ Angle
Flue
Air
Twin Flue
Vertical
Terminal
Twin Flue Mini
Terminals
MAX0045B
Ceiling
0.5/1.45m flue
duct set to correct
height and clipped
to air/flue pipes
1.5m Flue Pipe Ø60
1.47m Air Pipe Ø60
Cut Threaded Rod
to required length
Flue Bracket Pack
Part No. 5106207
Support Bracket
Assembly
Pipe
Clamps
Ø60
Fixing
Rail
Tee-Bolt
Wood Screw
Locking Nuts
Wall
Wall
Plug
2m maximum between
Support Brackets
300mm maximum between
Support Brackets & Bends
Support
Brackets
2m
Extension
300mm
maximum
Condensate
must
not be
allowed
to sit in the
bottom of the
Flue Pipes
Condensate
2˚ Angle
Flue Air
Flue Air
Twin Flue
Vertical
Terminal
Kit Contents
A
- Pipe Clamp Brackets
2 off
B
- Flue Pipe Cover Short
1 off
C
- Flue Pipe Cover Long
1 off
D
- Fixings Pack
1 off (not shown)
A
B
C
Flue Duct
This kit covers pipe lengths from 0.5 m to 1.45 m
1. Measure length of flue/air pipes to be
covered. Set the short and long covers to the
required length and secure through the
relevant holes using four of the self tapping
screws provided.
2. Attach the pipe clip brackets to the top and
bottom of the covers using the remaining four
self tapping screws provided.
3. Push the assembly onto the pipes until the
clips locate around the pipes.
Air/Flue Pipe Support
It is recommended that the air/flue pipes should
be clipped or otherwise supported at not more
than 2 m intervals.
Ensure that vertical lengths of flue are
adequately supported so that the joints cannot
“creep” in use.
Ensure that air/flue pipes are clamped within
300 mm of every bend. Obtain extra Flue
Bracket Packs (Part No. 5106207) as required.
Fig. 8
Guidance Notes on Twin Flue Installations