39
F
ault Finding Guide
DISPLAY
MESSAGE
ACTION / REMEDY
FURTHER ACTIONS
CODE
(INFORMATION / FAULT)
A 01
Burner failed to light
Check gas supply and gas valve operation
Check fan and spark operation. Check flue for blockage
Clean or replace ionisation probe & lead
Check condensate outlet not blocked & vent tube is clear
A 41
System flow fault
Check pump operation and speed setting
Check by-pass isolating valve is open
A 03
Over temp. lock-out or circulation failure
Check pump, 3-way valve & CH water pressure
Replenish system & purge air/water via manual vent
A 04
Overheat 'stat open/gas valve failure
Check wires/re-set 'stat. Test valve coils.
Test for 230V and Neutral at PCB & plug on gas valve
A 05
Safety relay failure (in boiler control)
Switch OFF/ON - press RESET
Replace boiler control Part No. 5107535
A 07
Heat exchanger monitoring fault
Check/adjust gas valve differential (page 42)
Clean/replace ionisation probe & lead Part No. 5106941
Test combustion at high and low input (page 42)
Check boiler control responds to flow & ret.sensors
A 15
CH pressure loss/pressure sensor faulty.
Check/replenish CH system pressure. Find leaks.
Check/replace pressure transmitter and cable.
A 19
Flame detected after gas valve shut
Relight, check gas valve closes promptly
Check for electric mains problem. Replace gas valve
A 20
Flame detected during ignition cycle
Check gas valve closes fully. Replace
Check ionisation probe & condensate outlet
A 33
Fan speed incorrect
Check fan wiring and connections
Replace fan Part No. 5106068 or boiler control
A 40
System response fault
Check pump operation and speed setting
Check 3-way valve operation. Purge air from H/E
Check by-pass and other water valves open.
Check boiler control responds to flow & ret.sensors
b 52
¡C Indicative cylinder temperature
O.K. Cylinder being re-heated
Press RESET button to scroll display
c 80
¡C Indicative flow temperature to CH
O.K. Scroll to pressure display "P"
Press RESET button to scroll display
E 01
Primary pressure too high
Reduce CH system pressure
Check/adjust/replace primary expansion vessel 5106287
E 03
Flow temperature abnormally high
Check pump, 3-way valve & CH system pressure
Replenish system, adjust pump speed & bleed air
E 04
Flow sensor open circuit
Check cable/connections not damaged
Renew sensor/cable. Check connections on control
E 06
Flow sensor short circuit
Check cable/connections not damaged
Renew sensor/cable. Check connections on control
E 07
DHW sensor open circuit
Check cable/connections not damaged
Renew DHW cable /sensor assy. Part No. 5106290
E 08
DHW sensor short circuit
Check cable/connections not damaged
Renew DHW cable /sensor assy. Part No. 5106290
E 20
Flame detected with closed gas valve
Check ionization probe/cable
Check condensate outlet not blocked & vent tube clear
E 21
Live & Neutral supply reversed
Correct the electrical supply
E 22
Electrical supply not 50Hz
Correct the electrical supply
E 29
Fault in link on 6-way plug J11
Replace (pressure sensor) cable assy.
Part No. 5107534
E 40
Return sensor open circuit
Check cable/connections not damaged
Renew sensor/cable. Check connections on control
E 41
Return sensor short circuit
Check cable/connections not damaged
Renew sensor/cable. Check connections on control
E 42
Internal control error
Switch OFF/ON at mains isolator
Replace boiler control Part No. 5107535
P 0.1 - 0.4 (bar) Boiler off because pressure too low
Replenish CH system & purge air
Find leak(s) and repair.
P 0.5 - 0.9 (bar) Water pressure in CH system low
Replenish CH system & purge air
Find leak(s) and repair. Compare analogue gauge pressure.
P 1.0 - 2.9 (bar) Normal pressure, system warm/hot
O.K.
P 3.0 - 3.5 (bar) Primary pressure over 3 bar, boiler off
Reduce CH system pressure
Check/adjust/replace primary expansion vessel
t 80
¡C Indicative flow temperature to DHW
O.K. Scroll to pressure display "P"
Press RESET button to scroll display
U 60
¡C DHW temperature selected (by knob)
Adjust if required - 55¡C recommended
Range: 65¡C (winter) - 45¡C (summer)
Other codes not listed above indicate a faulty boiler control
MAX0062D
F
ault Finding Diagnostic Codes