background image

5401591 - REV A

   •  

 

1/20

 page 5 OF 12

Potter Electric Signal Company, LLC

      •   

 St. Louis, MO

      •   

 Phone: 800-325-3936

      •   

 www.pottersignal.com

RBVS

Universal Ball Valve/Solenoid 

Coil Supervisory Switch

TYPICAL STANDARD 1/2” 

SOLENOID VALVE SHOWN

CLAMP-VEE SOLENOID (SMALL) (10)

1/2 NPT NIPPLE CONNECTION

SCREW-MACHINE (12)

CLAMP-VEE (SMALL) (1)

NUT-KEPS (20)

“L” BRACKET-MOUNTING

(13) 

BRACKET-SOLENOID MOUNTING (21) 

SWITCH ENCLOSURE

TAMPER RESISTANT SCREW 

(17)

ACTUATOR ACTIVATED ON STUD

IN SOLENOID COIL

INSERT NUTS #10-32 

INTO BOTTOM CLAMP (11)

Typical Solenoid Valve Mounting

Press Fit Hex Slots

Fig 6

Fig 7

Installation on Solenoid Valve

1.  For solenoid mounting use Bag colors, White, Clear and Red. See 

Mounting Configuration Table 1 (see page 2).

2. 

Use one clamp-vee (small) from the white bag as the top clamp and the 

(clamp-vee solenoid) as the bottom clamp from the clear bag. See Fig 6. 

3.  Insert both small rubber grippers from the white bag into both clamps. 
4. 

Insert two, #10-32 hex nuts from the clear bag into the bottom press fit 

hex slots of the (clamp-vee solenoid). Make sure the hex nuts are fully 

seated in the hex slots. See Fig 7. 

5. 

Insert screws into top mounting clamp-vee (small).

6. 

Place (clamp-vee solenoid) on bottom of the solenoid nipple.

7. 

Place top mounting clamp-vee (small) over solenoid nipple and insert the 

screws into (clamp-vee solenoid). Make sure the top of the clamp-vee 

(small) is parallel with the top of the solenoid coil. Tighten alternately to 

30 in-lbs. (minimum) of torque. 

8. 

Attach the “L” bracket-mounting to the top clamp-vee using the ¼-20 X 

¾” hex bolt and washer out of the Red bag. Do not fully tighten hex bolt. 

Make sure vertical slot on the “L” mounting-bracket is closer to the center 

of the solenoid coil. See fig 6.

9. 

Attach the (bracket-mounting solenoid) from the Red bag to the 

RBVS through the two smaller slots in the bracket with two tamper 

resistant screws.

10.  Slide the bracket up against the stop on the back of the RBVS and 

tighten the tamper resistant screws.

11.  Using two tamper resistant screws and keps nuts, loosely attach 

the  (bracket-mounting  solenoid)  to  the  “L”  bracket-mounting. 

See Fig 6.

12.  Remove the RBVS switch enclosure cover.
13.  position the RBVS so the actuator is directly above the coil 

mounting stud in the center of the solenoid coil. Tighten the hex 

bolt on the “L” mounting-bracket.

14. 

Slide the RBVS down the “L” mounting-bracket so the actuator is 

activated by the stud in the solenoid coil.

15.  While holding the RBVS enclosure down so that the actuator is 

depressed by the coil mounting stud, securely tighten the two 

tamper resistant screws and keps nuts.

16.  Wire main switch and tamper switch (if required). If required, 

carefully route tamper switch wires through strain relief slot 

in switch enclosure. Fully seat the wires into the bottom of the 

channel. See Fig 1. 

17.  Replace RBVS switch enclosure cover and securely tighten cover 

screws to 10 in-lbs minimum. See notice on page 6.

Typical Electrical Connections

CLAMP-VEE SOLENOID (10)

GRIPPER-RUBBER (SMALL) (2)

SCREW-MACHINE

 #10-32 X 1 3/4" (12)

NUT HEX #10-32 (11)

Summary of Contents for RBVS

Page 1: ...dd to the mounting flexibility of the RBVS See Typical Mounting Diagrams and Installations and Operation on following pages Technical Specifications Dimensions With Large Clamps 6 L x 5 W x 5 3 H 15 2 cm L x 12 7 cm W x 13 2 cm H With Small Clamps 6 L x 4 W x 5 3 H 15 2 cm L x 10 2 cm W x 13 2 cm H With Solenoid ClampAssembly 5 1 Lx 3 3 Wx 6 H 13 cm Lx 8 38 cm W x 15 24 cm H Shipping Weight 1 65 l...

Page 2: ...EPS 8 32 HEX STEEL ZINC PLATED 2 21 BRACKET SOLENOID MOUNTING 1 Pipe Size Valve Supervise Open Closed Valves Valve Handle Type Use Bag Color Use Item Number Item xQty Clamps Grippers Item xQty Brackets Item Hardware Item xQty 1 2 to 3 4 12 5 to 19mm Open Lever Fig 1 2 White Red Mounting Kit 1 x2 2 x2 13 3 x2 4 x2 16 17 x2 18 19 1 x2 2 x2 13 14 3 x2 4 x2 16 17 x2 18 x2 19 x2 Tee Fig 4 1 x2 2 x2 13 ...

Page 3: ...g but do not tighten fully 11 Place ball valve in the desired position to monitor 12 Position L bracket mounting so that it contacts the back edge of the valve handle and secure its hex bolt It may be necessary to close open valve to access this bolt 13 Slide loosely assembled RBVS switch enclosure to a position that permits the actuator to contact the valve handle Cut and remove the plastic coati...

Page 4: ...ntact the tee handle Cut and remove the plastic coating from the ball valve handle to allow the RBVS actuator to contact and be activated by the metal of the handle 11 Tighten L bracket mounting hex bolt to 30 in lbs Minimum of torque 12 Remove the RBVS switch enclosure cover 13 Slide RBVS enclosure down L bracket mounting until the housing contacts the tee valve handle Securely tighten the two ta...

Page 5: ...il Tighten alternately to 30 in lbs minimum of torque 8 Attach the L bracket mounting to the top clamp vee using the 20 X hexboltandwasheroutoftheRedbag Donotfullytightenhexbolt Makesureverticalslotonthe L mounting bracketisclosertothecenter of the solenoid coil See fig 6 9 Attach the bracket mounting solenoid from the Red bag to the RBVS through the two smaller slots in the bracket with two tampe...

Page 6: ...k dry pipe or preaction deluge valves Locations shall be as indicated on drawings and plans and as required by applicable local and national codes and standards The supervisory switch shall monitor the position of the handle on the valve and be capable of monitoring a valve in the open or closed position Movement of the valve handle from normal shall activate the supervisory switch Restoration of ...

Page 7: ...ypiques et Installations et fonctionnement sur les pages suivantes Spécifications techniques Dimensions Avec des grandes pinces 6 po x 5 po x 5 3 po 15 2 cm Lx 12 7 cm l x 13 2 cm H Avec des petites pinces 6 po x 4 po x 5 3 po 15 2 cm Lx 10 2 cm l x 13 2 cm H Avec l assemblage de la pince à électrovanne 5 1 po x 3 3 po x 6 po 13 cm Lx 8 38 cm l x 15 24 cm H Poids d expédition 0 74 kg 1 65 lb Encei...

Page 8: ...CROU KEPS NO 8 32 HEXAGONAUX EN MÉTAL PLAQUÉ ZINC 2 21 SUPPORT FIXATION DU SOLÉNOÏDE 1 Taille du tuyau vanne Vannes en position supervisée ouverte fermée Type de poignée de la vanne Utilisez la couleur du sac Utilisez le numéro d article Numéro d article quantité Colliers pinces Numéro d article quantité Supports Numéro d article Matériel Numéro d article quantité 1 2 po à 3 4 po 12 5 à 19 mm Ouvr...

Page 9: ...pas serrer entièrement 11 Placez le clapet à bille dans la position souhaitée pour surveiller 12 Placez le support de montage en L afin qu il entre en contact avec le bord arrière de la poignée de la vanne et fixez son boulon hexagonal Dans certains cas il peut être nécessaire de fermer d ouvrir la vanne afin d accéder au boulon 13 Faites glisser l enceinte de l interrupteur RBVS montée sans serra...

Page 10: ...ermet à l actionneur d entrer en contact avec la poignée en T Découpez et enlevez le revêtement en plastique de la poignée du clapet à bille afin de permettre à l actionneur RBVS d entrer en contact et d être activé par le métal de la poignée 11 Serrez le boulon hexagonal du support de montage en L à 30 po lb minium de couple 12 Enlevez le couvercle de l enceinte de l interrupteur RBVS 13 Faites g...

Page 11: ...n V à l aide d un boulon et d une rondelle hexagonale 20 X du Sac rouge Ne pas trop serrer le boulon hexagonal Veillez à ce que la fente verticale sur support de montage en L soit plus près du centre de la bobine de solénoïde Voir Image 6 9 Fixez le support de montage du solénoïde du Sac rouge au RBVS via les deux fentes plus petites dans le support à l aide de deux vis inviolables 10 Faites gliss...

Page 12: ...exigé par les normes et codes locaux et nationaux d application L interrupteur de surveillance des crosses devra surveiller l emplacement de la poignée sur la vanne et être capable de surveiller une vanne en position ouverte ou fermée Le mouvement de la poignée de la vanne à partir de l état normal devra activer l interrupteur de surveillance des crosses La réparation de la poignée de la vanne fer...