background image

RBVS

Universal Ball Valve/Solenoid 

Coil Supervisory Switch

5401591 - REV A

   •  

 

1/20

 page 1 OF 12

Potter Electric Signal Company, LLC

      •   

 St. Louis, MO

      •   

 Phone: 800-325-3936

      •   

 www.pottersignal.com

Description

The Model RBVS is designed to monitor the fully open or closed 

position of a ball valve installed in a sprinkler system as well as monitor 

the position of a coil on a solenoid for a preaction/deluge system. The 

unit will fit on most ball valves installed on back-flow-preventers and 

alarm trim lines of dry, alarm, and deluge sprinkler valves. The switch 

operates if the ball valve handle is moved from the normal position. 

However, the switch does not track the position of the handle or ball. 

When the ball valve handle is under the RBVS plunger, a spring-loaded 

actuator will contact the valve handle. When the handle is moved from 

the position, this actuator extends to the tripped position, and the RBVS 

contacts change state, thereby opening or closing a circuit. 
The unit also includes a small “L” bracket and “V” clamp to allow the 

RBVS to mount directly to the nipple on the coil of a solenoid valve. 

The plunger of the RBVS is actuated by the stud protruding through the 

center of the coil, see Fig. 6. If a technician removes the coil from the 

solenoid for testing, the RBVS will activate.
a cover tamper switch is available and is activated by the removal of the 

RBVS housing cover. If an attempt is made to remove the RBVS by the 

removal of the mounting brackets, the unit will be set into the tripped 

mode by this action.

The RBVS can be mounted to the hex portion of the ball valve or back-

flow-preventer or to the adjoining pipe via two clamps. The RBVS is 

shipped with three sets of mounting kits to accommodate various pipe 

and valve sizes, refer to Table 1. an “L” shaped and offset bracket for 

mounting the switch enclosure and an extension bracket add to the 

mounting flexibility of the RBVS. See “Typical Mounting Diagrams” 

and “Installations and Operation” on following pages. 

Technical Specifications

Dimensions

With Large Clamps: 6” L x 5” W x 5.3” H (15,2 cm L 

x 12,7 cm W x 13,2 cm H)
With Small Clamps: 6” L x 4” W x 5.3” H (15,2 cm L 

x 10,2 cm W x 13,2 cm H)
With Solenoid Clamp assembly: 5.1” L x 3.3” W x 6” 

H ( 13 cm L x 8,38 cm W x 15,24 cm H)

Shipping 

Weight

1.65 lbs.

enclosure

Non-Corrosive Composite Material

Temperature 

Range

-40°F to 150°F (-40°C to 65°C)

Optional 

Housing Cover 

Tamper

Cover incorporates tamper resistant fasteners 

that requires a special key for removal. One key 

is supplied with each device. For optional cover 

tamper switch kit, order Stock No. 0090224. See 

bulletin #5401598 

Contact 

Ratings

SPDT Contact: (Form C) 10.1A at 125 VAC

                     2A at 30 VDC Resistive

                     10 mAmps minimum at 24 VDC
SPDT Cover Tamper: 5A at 125 VAC
                                   1mA at 5 VDC min

environmental 

Limitations

NeMa 4 (Ip66)

Not for use in hazardous locations

Use suitably rated conduit and connections 

Conduit 

entrance

One Knockout for 1/2” conduit connection provided

(See Notice on page 6)

*Specifications subject to change without notice.

Features

• 

assembled in USa

• 

Fits most lever/tee type ball valves up to 2”

•  Fits most backflow preventers up to 2”
• 

Operates on open or closed valves

• 

Includes mounting hardware to supervise coils on most 

solenoids

• 

accommodates up to 12 aWg wire

•  Optional field installed cover tamper switch kit (0090224)
• 

RoHS compliant

Important: 

This document contains important information on the installation and operation of the RBVS Universal Ball Valve/Solenoid Coil Supervisory 

Switches. please read all instructions carefully before beginning installation.  a copy of this document is required by NFpa 72 to be maintained on site.

Before any work is done on the fire sprinkler or fire alarm system, the 

building  owner  or  their  authorized  representative  shall  be  notified. 

Before opening any closed valve, ensure that opening the valve 

will not cause any damage from water flow due to open or missing 

sprinklers, piping, etc.

NOTICE

Summary of Contents for RBVS

Page 1: ...dd to the mounting flexibility of the RBVS See Typical Mounting Diagrams and Installations and Operation on following pages Technical Specifications Dimensions With Large Clamps 6 L x 5 W x 5 3 H 15 2 cm L x 12 7 cm W x 13 2 cm H With Small Clamps 6 L x 4 W x 5 3 H 15 2 cm L x 10 2 cm W x 13 2 cm H With Solenoid ClampAssembly 5 1 Lx 3 3 Wx 6 H 13 cm Lx 8 38 cm W x 15 24 cm H Shipping Weight 1 65 l...

Page 2: ...EPS 8 32 HEX STEEL ZINC PLATED 2 21 BRACKET SOLENOID MOUNTING 1 Pipe Size Valve Supervise Open Closed Valves Valve Handle Type Use Bag Color Use Item Number Item xQty Clamps Grippers Item xQty Brackets Item Hardware Item xQty 1 2 to 3 4 12 5 to 19mm Open Lever Fig 1 2 White Red Mounting Kit 1 x2 2 x2 13 3 x2 4 x2 16 17 x2 18 19 1 x2 2 x2 13 14 3 x2 4 x2 16 17 x2 18 x2 19 x2 Tee Fig 4 1 x2 2 x2 13 ...

Page 3: ...g but do not tighten fully 11 Place ball valve in the desired position to monitor 12 Position L bracket mounting so that it contacts the back edge of the valve handle and secure its hex bolt It may be necessary to close open valve to access this bolt 13 Slide loosely assembled RBVS switch enclosure to a position that permits the actuator to contact the valve handle Cut and remove the plastic coati...

Page 4: ...ntact the tee handle Cut and remove the plastic coating from the ball valve handle to allow the RBVS actuator to contact and be activated by the metal of the handle 11 Tighten L bracket mounting hex bolt to 30 in lbs Minimum of torque 12 Remove the RBVS switch enclosure cover 13 Slide RBVS enclosure down L bracket mounting until the housing contacts the tee valve handle Securely tighten the two ta...

Page 5: ...il Tighten alternately to 30 in lbs minimum of torque 8 Attach the L bracket mounting to the top clamp vee using the 20 X hexboltandwasheroutoftheRedbag Donotfullytightenhexbolt Makesureverticalslotonthe L mounting bracketisclosertothecenter of the solenoid coil See fig 6 9 Attach the bracket mounting solenoid from the Red bag to the RBVS through the two smaller slots in the bracket with two tampe...

Page 6: ...k dry pipe or preaction deluge valves Locations shall be as indicated on drawings and plans and as required by applicable local and national codes and standards The supervisory switch shall monitor the position of the handle on the valve and be capable of monitoring a valve in the open or closed position Movement of the valve handle from normal shall activate the supervisory switch Restoration of ...

Page 7: ...ypiques et Installations et fonctionnement sur les pages suivantes Spécifications techniques Dimensions Avec des grandes pinces 6 po x 5 po x 5 3 po 15 2 cm Lx 12 7 cm l x 13 2 cm H Avec des petites pinces 6 po x 4 po x 5 3 po 15 2 cm Lx 10 2 cm l x 13 2 cm H Avec l assemblage de la pince à électrovanne 5 1 po x 3 3 po x 6 po 13 cm Lx 8 38 cm l x 15 24 cm H Poids d expédition 0 74 kg 1 65 lb Encei...

Page 8: ...CROU KEPS NO 8 32 HEXAGONAUX EN MÉTAL PLAQUÉ ZINC 2 21 SUPPORT FIXATION DU SOLÉNOÏDE 1 Taille du tuyau vanne Vannes en position supervisée ouverte fermée Type de poignée de la vanne Utilisez la couleur du sac Utilisez le numéro d article Numéro d article quantité Colliers pinces Numéro d article quantité Supports Numéro d article Matériel Numéro d article quantité 1 2 po à 3 4 po 12 5 à 19 mm Ouvr...

Page 9: ...pas serrer entièrement 11 Placez le clapet à bille dans la position souhaitée pour surveiller 12 Placez le support de montage en L afin qu il entre en contact avec le bord arrière de la poignée de la vanne et fixez son boulon hexagonal Dans certains cas il peut être nécessaire de fermer d ouvrir la vanne afin d accéder au boulon 13 Faites glisser l enceinte de l interrupteur RBVS montée sans serra...

Page 10: ...ermet à l actionneur d entrer en contact avec la poignée en T Découpez et enlevez le revêtement en plastique de la poignée du clapet à bille afin de permettre à l actionneur RBVS d entrer en contact et d être activé par le métal de la poignée 11 Serrez le boulon hexagonal du support de montage en L à 30 po lb minium de couple 12 Enlevez le couvercle de l enceinte de l interrupteur RBVS 13 Faites g...

Page 11: ...n V à l aide d un boulon et d une rondelle hexagonale 20 X du Sac rouge Ne pas trop serrer le boulon hexagonal Veillez à ce que la fente verticale sur support de montage en L soit plus près du centre de la bobine de solénoïde Voir Image 6 9 Fixez le support de montage du solénoïde du Sac rouge au RBVS via les deux fentes plus petites dans le support à l aide de deux vis inviolables 10 Faites gliss...

Page 12: ...exigé par les normes et codes locaux et nationaux d application L interrupteur de surveillance des crosses devra surveiller l emplacement de la poignée sur la vanne et être capable de surveiller une vanne en position ouverte ou fermée Le mouvement de la poignée de la vanne à partir de l état normal devra activer l interrupteur de surveillance des crosses La réparation de la poignée de la vanne fer...

Reviews: