POM2-3333
Merger Unit Test User
Manual
30
3.5 GOOSE abnormal
3.5.1 Testing wiring connection
POM2-3333
MU
GOOSE
3.5.2 Test configuration
Keep the configuration the same.
While making the independent test, the users only need select configuration zone to
choose the message type. There are IEC61850-9-2 and IEC60044-8 available. Refer to
part 3.1.2.2.
3.5.3 Start test
3.5.3.1 Parameters
Please refer to part 3.1.3.1.
3.5.3.2 Start test
1. Press button
on the test interface
or
on the tester POM2-3333 or F2 on the
externally PC to run the test
Detect and select the test GOOSE control block
In this figure, select Detection mode first. Stop the software until GOOSE is detected.
Select the test GOOSE control block and run the software after choosing the Receive
mode.
3.5.3.3 Real-time monitoring data