POM2-3333
Merger Unit Test User
Manual
13
3.1.2 Test configuration
3.1.2.1 IEC Configuration (MU input)
Press
in the toolbar and configure with following steps:
Step 1: Select the output type
Analog output, IEC61850-9-2, IEC 60044-8 (State grid), IEC61850-9-2,
IEC60044-8 (State grid)
Select the MU type to make choice. If the same module type is chosen as the MU
sampling input type, it is not necessary to choose it again, only to keep the same
output type.
When the analog output is select, then go ahead with step 2.
If the selected output includes IEC61850-9-2 or IEC60044-8 (State grid), the
communications parameters and channels should be confirugred in the
corresponding message. After the configuration, continue with step 2. Please refer to
the configuration instruction in appendix:
The configuration for sending messages
.
Step 2: Set the ration in each voltage and current output channel
The voltage, current channel and the group number are corresponding to the
channels in figure 3-2. While setting ratio, please set the corresponding voltage/
current’s ratio. Please refer to the channel allocation in part 3.1.2.2.
3.1.2.2 Message receive type and channel configuration (MU output)