54
1. Wire AirTouch 4, gateway and AC indoor as per diagram below and leave the
dipswitches on the gateway at their default position. Make sure all wires are
connected properly.
2. Check the temperature compensation value setting (SW6 switch) on the indoor
PCB and make sure its value is set to EEPROM DEFAULT as per the instructions
on the wiring label at the back of the electrical box cover.
3. In default, AC will use its own return air sensor as control sensor. Installers can
set the AC control thermistor to an AirTouch 4 sensor by going to AC setup in
Installer’s Settings of AirTouch 4.
4. If the sensor on the AC wall controller is used for AC control (Follow Me feature
on the AC wall controller), please: Press the Follow Me button on the wall
controller to activate Follow Me. The displayed value for home temperature will
be the measured temperature where the AC wall controller installed.
(657222) Commissioning Notes
Wiring Diagrams contd.