23
PULL-TO-OPEN LIMIT SETTING
(Open gate to inside of property)
Single Gate Installations
Step 1
Make sure the gate is in the fully open position.
Ensure power switch is in the ON position.
Step 2
Verify Block 2, DIP Switch #1 is in OFF position. Press the
cycle button on circuit board and the gate will begin to
close. Stop the gate using the cycle button when the desired
limit has been reached.
Step 3
Press and hold the “SET LIMIT” button until one audible
beep is heard to acquire the closed limit setting. The STATUS
light will turn on immediately upon pressing the SET LIMIT
button. The STATUS light will turn off and an audible beep
will verify the closed limit is now set.
Step 4
Press cycle button on circuit board to return the gate to the
fully open position.
Step 5
Again, using the cycle button close the gate to verify it
meets the desired location. If the gate did NOT reach the
desired closed limit, proceed to step 6.
Step 6
CLEARING THE CLOSED LIMIT SETTING:
a) Return the gate to the fully open position.
b) Press and hold the SET LIMIT button until two audible
beeps are heard.
c) Two audible beeps will verify the closed limit setting is
now cleared.
Repeat steps 1 – 5 to program the gates “closed limit
setting”.
Figure 27
PULL-TO-OPEN LIMIT SETTING
WARNING: Do not use hand held
transmitters to program primary
and secondary limits. Only the
cycle button should be used until
final set up is complete to avoid
damage to actuators and voiding
warranty.
***Dip switch number 6 dictates which gate is being
affected by the set limit button, whether setting or
clearing the limit. If dip switch 6 is in the up position, it
will set or clear the limit for the secondary operator. If
it’s in the down position it will set ot clear the limit for
the primary operator.***